background image

7

Sales 800-633-0405

www.productivity2000.com

DISPLAY   
UNITS
DECIMAL
COUNTS 

Momentarily Press 

SEL

 button to

toggle through

secondary displays

DISPLAY
STATUS
INFO

DISPLAY
SETUP
INFO

Hold 

SEL

 button down to cycle through primary screens. Release button to select screen.

Power On

PASSED
SELF
TEST

Appears

initially

P2-04AD-1
 
Fw. Rev.
 1.00

16-BIT
0-20mA
3 CH
ENABLED

DISPLAY
UNITS
MILIAMP
0-20mA

These screens will 

then auto cycle

Error Messages:

An existing error will 

be inserted into the 

cycling Status Info 

screen.

This screen will 

auto cycle with

status information

1  00000

2  00000

3  00000

4  SPARE

1 0000H

2 0000H

3 0000H

4 SPARE

1 0.00mA

2 0.00mA

3 0.00mA

4  SPARE

End of
Status
Menu
List

MISSING
EXTERNAL
24VDC

SELFTEST
FAIL
REPLACE
MODULE

MISSING
CONFIG
DATA

DISPLAY
UNITS
HEX
COUNTS

End of
Status
Menu
List

OLED Panel Display

Summary of Contents for Productivity2000 P2-04AD-1

Page 1: ...ion is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product Removable...

Page 2: ...61010 2 201 Safety Input Specifications Input Channel 4 Input Ranges 0 20 mA Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 20 mA 0 305 μA per count 1 LSB 1 count Data Range 0 to 65535 counts Input Type Sinking Single ended 1 common Maximum Continuous Overload 31mA Input Impedance 250Ω 0 1 1 4 W Hardware Filter Characteristics Low Pass 3dB 100Hz Sample Duration Time 9ms p...

Page 3: ...ng fuse is recommended for current loops 24VDC User Supplied Power User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM I1 I2 I3 I4 COM COM 0V 24V 24 VDC User Supplied Power CH1 ADC CH2 ADC CH3 ADC CH4 ADC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM 1 2...

Page 4: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top locking tab toward mod...

Page 5: ... 1 module into the base configuration Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20 1 ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P2 CBL18 1P ZL P2 CBL18 2P 3 Screw Terminal Block only P2 RTB Quantity 1 4 Spring Clamp Term...

Page 6: ... 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Mak...

Page 7: ...2 04AD 1 Fw Rev 1 00 16 BIT 0 20mA 3 CH ENABLED DISPLAY UNITS MILIAMP 0 20mA These screens will then auto cycle Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information 1 00000 2 00000 3 00000 4 SPARE 1 0000H 2 0000H 3 0000H 4 SPARE 1 0 00mA 2 0 00mA 3 0 00mA 4 SPARE End of Status Menu List MISSING EXTERNAL 24VDC SELF...

Page 8: ...ision Date P2 04AD 1 DS 1st Edition Rev A 2 11 2022 Copyright 2019 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1 bit per channel Module Failed 1 bit per module Missing 24V 1 bit per module ...

Reviews: