DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
10
Wiring Examples
DC/AC Voltage Input Wiring (Ranges: 2, 20, 200, 600 V)
Note:
MAXIMUM VOLTAGE APPLICABLE IS: 600V DC/ AC
Terminals CN2
1 2 3 4 5
N
L
V
Voltmeter 20/ 200/ 600 V
DC/ AC
Terminals CN2
1 2 3 4 5
V
N
L
Voltmeter 2 V
DC/ AC
DC/AC Current Input Wiring (Ranges: 1A, 5A)
Terminals CN2
1 2 3 4 5
I
N
L
1/5 A DC/ AC
DC/AC Direct Connection
Connection using and AC Current Transformer
Terminals CN2
1 2 3 4 5
I
N
L
1A / 5A AC MAX.
R
1
R
2
Important:
When using a current transformer, the input impedance (Ri) of the DPM3 is 14 mOhms.
To maintain measurement accuracy, use connecting wires of appropriate gauge and length to
prevent the total resistance of the measuring circuit (R1+R2+Ri) from exceeding the Burden
rating of current transformer .
DC/AC Current Input Wiring (Range: 200mA)
Terminals CN2
1 2 3 4 5
I
N
L
200mA DC/AC