Relay Terminal Blocks

A-45

ABS Series

ABL Series

ASL Series

Power Relay

SSR

I/O Terminal Blocks

Interface  

Terminal Blocks
Common  

Terminal Blocks
Sensor Connector  

Terminal Blocks

Relay  

Terminal Blocks

I/O Cables

Connector Type  

Cables
Open Type  

Cables

Others

-|Transparent setting guide|-

 Specifications

Model 

ABL-L04PQ-UN

ABL-L04PQ-UY

1

ABL-L04R6-UN

ABL-L04R6-UY

1

Power supply

24VDC

 ±10%

Rated load voltage&current

2

250VAC

 50/60Hz 5A, 30VDC

 5A

Current consumption

3

≤ 20mA

Output type

1a contact relay output

Applied relay

PQ1a-24V [MATSUSHITA (Panasonic)]

G6B-1174P-FD-US [OMRON]

No. of relay points

4-point

Terminal type

Screwless

Terminal pitch

10.2mm

Indicator

Operation indicator: blue LED

Applied 

cable

Solid wire

Ø0.6 to Ø1.25mm (60

 only)

Stranded wire

4

AWG22-16 (0.3 to 1.25mm

2

) (60

 only)

Stripped wire length

8 to 10mm

Insulation resistance

≥ 1,000MΩ (at 500VDC megger)

Insulation 

resistance

between 

coil-contacts

4,000VAC 50/60Hz for 1 minute

3,000VAC 50/60Hz for 1 minute

Between

same contacts

5

1,000VAC 50/60Hz for 1 minute

1,000VAC 50/60Hz for 1 minute

Vibration

Mechanical

1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours

Malfunction

1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minutes

Shock

Mechanical

1,000m/s

(approx. 100G) in each X, Y, Z direction for 3 times

Malfunction

100m/s

(approx. 10G) in each X, Y, Z direction for 3 times

Environ-

ment

Ambient temp.

-15 to 55

, storage: -25 to 65

Ambient humi.

35 to 85%RH, storage: 35 to 85%RH

Material

Terminal block: polyamide 66, conducting plate: brass, case&base: modified polyphenylene oxide

Accessory

Jumper bar: 1

Protection structure

IP20 (IEC standard)

Approval
Weight

6

Approx. 148g (approx. 92g)

Approx. 150g (approx. 94g)

Approx. 143g (approx. 87g)

Approx. 144g (approx. 88g)

 Rated load current 3A

 Rated load current 5A

1: This is for load protection and it is recommend to use at the inductive load.   

2:  Relay load capacity for resistive load. 

Please connect to a load using the same power supply. Connecting to a load from a different power supply may cause safety issues. 

3: The current consumption including LED current by one relay.

4: When using stranded wire, use End Sleeve (ferrule terminal) crimp terminals.

5: In case of ABL-L04   -   Y (varistor installed type), this is 300VAC.   

※6

: The weight includes packaging. The weight in parenthesis is for unit only. 

Environment resistance is rated at no freezing or condensation.

Model

ABL-L01PA-NN

ABL-L01PA-NY

1

ABL-L01PA-PN

ABL-L01PA-PY

1

ABL-L01TN-NN

ABL-L01TN-NY

1

ABL-L01TN-PN

ABL-L01TN-PY

1

ABL-L04PA-UN

ABL-L04PA-UY

ABL-L04TN-UN

ABL-L04TN-UY

ABL-H16R6-NN

ABL-H16R6-PN

Power supply

24VDC

 ±10%

Rated load voltage&current

2

250VAC

 50/60Hz 3A, 30VDC

 3A

Current consumption

3

≤8mA

≤20mA

Output type

1a contact relay output

Applied relay

APAN3124

[MATSUSHITA(Panasonic)]

NYP24W-K

[TAKAMISAWA(Fujitsu)]

APAN3124

[MATSUSHITA(Panasonic)]

NYP24W-K

[TAKAMISAWA(Fujitsu)]

G6B-1174P-FD-US 

[OMRON]

No. of relay points

1-point

4-point

16-point

Terminal type

Screwless

Terminal pitch

9.0mm (arranging over 2 units)

5.0mm

≥7.8mm

Indicator

Operation indicator: blue LED

Operation indicator: blue LED

Power indicator: red LED, 

operation indicator: blue LED

Applied 

cable

Solid wire

Ø0.6~Ø1.25mm (60

 only)

Stranded wire

4

AWG22-16 (0.3~1.25mm

2

) (60

 only)

Stripped wire length

8 to 10mm

Insulation resistance

≥ 1,000MΩ (at 500VDC megger)

Dielectric 

strength

Between 

coil-contact

3,000VAC 50/60Hz for 1 minute

Between  

same contacts

1,000VAC 50/60Hz for 

1 minute

750VAC 50/60Hz for 1 

minute

1,000VAC 50/60Hz for 

1 minute

750VAC 50/60Hz for 1 

minute

1,000VAC 50/60Hz for 

1 minute

Vibration Mechanical 

1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours

Malfunction

1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minutes

Shock

Mechanical

1000m/s

2

 (approx. 100G) in each X, Y, Z direction for 3 times

Malfunction

100m/s

2

 (approx. 10G) in each X, Y, Z direction for 3 times

Environ-

ment

Ambient temp.

-15 to 55

, storage: -25 to 65

Ambient humi.

35 to 85%RH, storage: 35 to 85%RH

Material

Terminal block: polyamide 66, conducting plate: brass, 

case&base: poly phenylene sulfide

Terminal block: polyamide 66, conducting plate: brass,

case&base: poly phenylene sulfide

Terminal block, cover: 

polycarbonate / 

CASE&BASE: modified 

polyphenylene oxide

Accessory

-

Jumper bar: 1

Jumper bar: 2

Protection structure

IP20 (IEC standard)

Approval
Weight

6

Approx. 138g 

(approx. 21g)

Approx. 135g 

(approx. 21g)

Approx. 125g

(approx. 72g)

Approx. 128g

(approx. 75g)

Approx. 446g 

(approx. 348g)

Summary of Contents for ABL Series

Page 1: ...Rail or screw mounting Relay Fujitsu NYP24W K Panasonic APAN3124 PQ1a 24V Omron G6B 1174P FD US 16 point Rated load voltage 3A Relay protection with the cover Easy relay replacement with relay ejector...

Page 2: ...using stranded wire use End Sleeve ferrule terminal crimp terminals 5 In case of ABL L04 Y varistor installed type this is 300VAC 6 The weight includes packaging The weight in parenthesis is for unit...

Page 3: ...ated load current 3A ABL L01TN PA Jumper bar model JB 9 0 04L For the desired application power load common jumper bar is sold separately 4 31 9 27 4 2 2 0 5 1 2 6 12 5 2 ABL L04TN PA Jumper bar model...

Page 4: ...or ABL L04 UY varistor installed type NPN PNP LOAD common are operated by the inserting position of the Jumper bar Please refer to the 2 Using jumper bars of Replacing Relay and Using Jumper Bar Jumpe...

Page 5: ...arts are only for ABL L04 UY varistor installed type NPN PNP LOAD common are operated by the inserting position of the Jumper bar Please refer to the 2 Using jumper bars of Replacing Relay and Using J...

Page 6: ...H16R6 NN ABL H16R6 PN 3 4 1 2 RY1 GND1 24VDC1 24VDC2 GND2 N C1 N C3 R1 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16 R2 R1 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16 R2 N C2 N C4 JP1 JP2 JP3...

Page 7: ...indicator guide Relay type color 1 1 Using jumper bar The right figure example is for 4 ABL L01 units with jumper bar For power common insert a jumper bar to top For load common insert it to bottom A...