Device Name Settings
To connect to the PROFINET network, configure the PROFINET interface. The PROFINET device name can be configured using the following methods.
■
Rotary switches
Be sure to place the seal of the protective cover firmly on the rotary switches after completing the settings.
The protection rating is not guaranteed when the protective cover is open.
x100
x10
x1
01. Rotate the rotary switches to set the device name. The green LED of the US indicator flashes.
Setting mode
Rotary switches Description
Value
PROFINET Device Name
000
This device name is stored in the ADIO-PN's EEPROM.
Applying the device name configured on the PROFINET Master or DCP tools.
PROFINET device name
001 to 999
Establish the communication connection after setting the ADIO-PN's device name.
The value of rotary switches is displayed at the last of the device name.
ADIO-PN-MA08A-ILM-
□□□
02. Turn on the ADIO-PN again.
03. Check that green LED of the US indicator is ON.
04. The device name has been changed.
05. Put the protective cover on the rotary switches.
■
atIOLink
The PROFINET device name configured by the atIOLink software is stored in the ADIO-PN's EEPROM. For more information, refer to the atIOLink User Manual.