Product Components
• Product (+ bracket)
• Instruction manual
Unit Descriptions
3
4
5
8
9
10
11
6
7
1
2
No. Name
Function
1
Time progressing display part
Shows progressing time
2
Time setting display part
Shows the setting time
3
Time unit
Shows time unit (h: hour / m: min / s: sec)
Flashing: time progressing
4
Operation mode
Shows current output operation mode
• INTG: no mark
5
Output contact
Shows the status of current output contact
6
UP / DOWN
Shows UP / DOWN mode of time progressing
7
Key lock
Shows key lock status
8
[RST] key
Initializes progressing time and output return
9
[MD] key
Enter RUN mode ↔ Parameter setting
Shift to next parameter in parameter setting
10
[◀] key
Enter RUN mode ↔ setting time change mode
Move the digit when changing the setting value.
11
[▲] key
Change the parameter setting value
Dimensions
•
Unit: mm, For the detailed drawings, follow the Autonics website.
□48
□52
56
14
□44.8
6
2
■
Bracket
■
Panel cut-out
30.5
60.3
□49.5
≥ 65
≥
65
□45
+ 0.5
0
□45
+ 0.5
0
Mode Setting
RUN
[MD] 3 sec
→
Parameter setting
[MD] 3 sec
→
RUN
[◀]
→
Time setting
01)
[MD]
→
While pressing [MD]
→
Check output
contact status
02)
Release [MD]
→
[RST]
→
Initialization
Auto
→
02) Only for the LE4SA model
01) If no key is pressed over 60 sec, returning to RUN mode and not storing the setting value.
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.
LE4S
❶
❶ Output
No mark: Time limit 1c
A: Time limit 2c, Time limit 1c + Instantaneous 1c
Output Operation Mode
For the detailed timing chart for operation output mode, refer to the manual.
The output operation mode differs depending on each model.
Group
Output operation mode
LE4S
LE4SA
Time setting
Group 1
OND
ON Delay
○
○
Time
OND.1
ON Delay 1
-
OND.2
ON Delay 2
○
INT
Interval
INT.1
Interval 1
-
OFD
OFF Delay
INTG
Integration time
Group 2
FLK
Flicker
○
○
tOFF
,
tON
FLK.1
Flicker 1
NFD
ON - OFF Delay
-
OnD
,
OFfD
NFD.1
ON - OFF Delay 1
Group 3
S-D
Star - Delta
-
○
T-1
,
T-2
TWN
Twin
TWN.1
Twin 1
Parameter Setting
•
Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
•
In the parameter setting, the time and output control continue.
•
If the settings are changed, all outputs to be OFF and reset the current values when
returning to RUN mode.
•
[MD] key: saves current setting value and moves to the next parameter.
Parameter
Display
Defaults
Setting range
Model
Display
condition
1-1
Output
operation
mode
OUtM
OND
•
Refer to the output
operation mode.
Comm.
-
1-2
Time range
tRNG
9(99
•
Refer to the table
below.
1-1. Output
operation
mode: Group 1
1-3
One-shot
output
time
OUTt
0)50
0.01 to 99.99 sec
1-1. Output
operation
mode: OND.2
1-4
T.off
time range
OfRG
9(99
•
Refer to the table
below.
1-1. Output
operation
mode: Group 2
1-5
T.on
time range
OnRG
9(99
1-6
T1
time range
T!RG
9(99
[LE4SA] 1-1. Output
operation
mode: Group 3
1-7
T2
time range
T@RG
9(99
[LE4SA]
1-8
Time
UP / DOWN
U-D
UP
UP: 0 → setting time
DN: setting time → 0
Comm. -
1-9
Width of
min. input
signal
InT
20
1, 20 ms
•
Set the min. width of
RESET, START, INHIBIT
input signals
[LE4S] -
1-10 Output
contact
01)
CONT
1c1C
1C.1C: Time limit 1c +
Instantaneous 1c
2C: Time limit 2c
[LE4SA] -
1-11 Backlight
BLU
ON
ON, OFF
Comm. -
1-12 Key lock
LOCK
lOFF
L.OFF: release key lock
LOC.1: lock [RST] key
LOC.2: lock [◀], [▲] key
LOC.3: lock [RST], [◀],
[▲] key
[LE4S]
-
LOc1
[LE4SA]
Unit
SEC
SEC
SEC
SEC
M S
M
M
Display
9.999
99.99
999.9
9999
99m59s 999.9m 9999m
Range
0.001s to
9.999s
0.01s to
99.99s
0.1s to
999.9s
1s to
9999s
0m1s to
99m99s
0.1m to
999.9m
1m to
9999m
Unit
H M
H
H
H
Display
99h59m 99.99h
999.9h
9999h
Range
0h1m to
99h59m
0.01h to
99.99h
0.1h to
999.9h
1h to
9999h
•
[Table]
01) 1-1. Output operation mode of group 3: 2C fixed