Connections
Caution
: Refer to the 'specifications' for checking the power supply and control output.
■
LE4S
RESET
START
INHIBIT
SOURCE
1
2
3
4
5
6
7
8
■
LE4SA
•
Output operation mode
: OND / OND.2
/ FLK / FLK1 / INT / TWN / TWN.1
(TWN, TWN.1 mode: time limit 2c fixed)
•
Output operation mode
: Y -∆ (Time limit 2c fixed)
•
Use the A contact.
SOURCE
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
∆
Y
SOURCE
Specifications
Model
LE4S
LE4SA
Function
MULTI time, MULTI operation
Display method
LCD (Backlight)
Return time
≤ 100 ms
Time operation
Signal ON Start
Power ON Start
Input signal
START, INHIBIT, RESET
Min. signal width
≈ 1, 20 ms
-
No-voltage input
Short-circuit impedance: ≤ 1 kΩ
Short-circuit residual voltage
: ≤ 0.5 VDCᜡ
Open-circuit impedance: ≥ 100 kΩ
-
Control output
Relay
Contact type
Time limit SPDT (1c)
Time limit DPDT (2c),
Time limit SPDT (1c) +
Instantaneous SPDT (1c)
(depends on operation mode)
Contact capacity
250 VACᜠ 5 A,
30 VDCᜡ 5 A resistive load
250 VACᜠ 3 A,
30 VDCᜡ 3 A resistive load
Error
Repeat
Power ON Start
: ≤ ± 0.01% ± 0.05 sec
Signal ON Start
: ≤ ± 0.005% ±0.03 sec
≤ ± 0.01% ± 0.05 sec
SET
Voltage
Temp.
Approval
ᜢ ᜧ ᜫ
Unit weight
≈ 98 g
Model
LE4S
LE4SA
Power supply
24 - 240 VACᜠ ± 10% 50 / 60 Hz, 24 - 240 VDCᜡ ± 10%
Power consumption
AC: ≤ 4.5 VA, DC: ≤ 2 W
AC: ≤ 4 VA, DC: ≤ 1.6 W
Insulation resistive
100 MΩ (500 VDCᜡ megger)
Dielectric strength
2000 VACᜠ 50 / 60 Hz for 1 min
Noise immunity
± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲)
Vibration
0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X,
Y, Z direction for 1 hour
Vibration (malfunction)
0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X,
Y, Z direction for 10 min
Shock
300 m/s
2
(≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)
100 m/s
2
(≈ 10 G) In each X, Y, Z direction for 3 times
Relay life cycle
Mechanical: ≥ 10,000,000 operations
Electrical: ≥ 100,000 operations
Ambient temperature
-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity
35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Time Setting
■ Setting method
•
Be aware that the time is progressing when you set the time.
•
If no key is pressed over 60 sec, returning to RUN mode and not storing the setting value.
1. In the parameter setting, set the output operation mode.
2. In RUN mode, press [◀] key to enter the time setting mode.
3. The last digit flashes at the time setting display part.
4. Set the time.
[
◀] key: shift the setting digit,
[
▲] key: shift the flashing position, increasing time
5. Press [MD] key to complete the setting and return to RUN mode.
■ Setting example
•
Output operation mode FK, FK1
Mode
Time progressing
display part
Time setting
display part
Description
RUN mode
-
-
Press [◀] key to enter the time setting
Setting mode
tOFF
00
m
01
s
Flashing: the last number
tOFF
01
m
20
s
Set the time via [◀],
[
▲] key
Press [
MD] key to complete the setting
and progress the next time setting
tON
00
m
01
s
Flashing: the last number
tON
03
m
57
s
Press [
MD] key to complete the setting
and return to RUN mode
Input Connections (LE4S)
When wiring, make sure that the power and the signal input terminals are non-insulated.
■ No-voltage (NPN) input
•
Solid-state input
Sensor
(NPN open collector output)
LE4S
INHIBIT
START
RESET
Q1
12-24 VDCᜡ
0 V
LE4S
INHIBIT
START
RESET
Q2
R
L
0 V
Sensor
(NPN output)
12-24 VDCᜡ
Q1-2: operates when it is ON.
•
Contact input
LE4S
INHIBIT
START
RESET
S3
S2
S1
0 V
Use reliable contact enough to flow 5 VDCᜡ 1 mA
Q1-2, S1-3: operates when it is ON.