background image

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002

www.autonics.com  |  +82-2-2048-1577  |  sales@autonics.com

-|Transparent Guide|-

-|Transparent Guide|-

Filter

Filters: Fog, Particle can be applied duplicated depending on the surrounding 
environment and detection object.
In case of multiple filters applied, 1. Fog filter 2. Particle filter is applied in order.
• When a filter is applied, the output cannot be reverted to the original scan data.

  

■ Fog filter

Reduces the laser reception sensitivity to avoid detecting fog, rain, and snow to 
prevent obstacle detection errors.
• Default: 3
• Setting range

 

 

SV

0

1

2

3

4

5

6

Max. detection distance [cm]

 01)

400

370

350

320

300

270

250

 01) At object reflectivity:  5 %

  

■ Particle filter

It uses continuous scan data to block the measurement of fine objects such as static 
objects or dust when detecting backgrounds.
• Default: 5
• Setting range

 

 

SV

1

2

3

4

5

Level

OFF

Low

<

<<

High

Function

It is set in the LiDAR sensor management software atLiDAR.
For more information, refer to the atLiDAR software manual.

  

■ Output

Set the output type between obstacle detection output (OUT 1) and error status 
output (OUT 2).

Obstacle detection output (OUT1) Error status output (OUT2) 

 01)

Normally open

Normally open (default)
Normally closed

Normally closed

Normally open
Normally closed

 01)  In case of Pulse of OUT2 (error status output) as ON,

 

it repeats open-close operation for 1 sec at the normal operation and it closes at error status.

  

■ Field output activation

Set the relay output ON/OFF when detecting an obstacle.
• Default: ON
• Setting range: ON / OFF

  

■ Anti-Masking error

An anti-masking error occurs when obstacle detection is not possible due to a foreign 
object on the front window of the device.
• Default: ON
• Error occurrence condition

 

-  Anti-masking error occurs when an object is detected within about 15 cm from the 

front window for more than 3 seconds

• Error clearing condition

 

-  Anti-masking error is cleared when no object is detected within about 15 cm from 

the front window for more than 5 seconds

  

■ Background error

When the initial set reference distance of background teaching data is changed, 
background error occurs.
• Default: ON
• Error occurrence condition

 

-   If the reference distance value is changed by 60 cm or more for about 3 seconds 

or more at one of the initial background teaching values (the reference distance 
of the scan angle 0 / 45 / 90 °), it is determined that the position of the device has 
changed and a background error occurs.

• Error clearing condition

 

-   If the reference distance data is within 'reference distance data during te 

about 30 cm' for longer than about 5 seconds, the background error is cleared.

  

■ Sensor position

Set the actual installed device position: view (top or bottom) and installation (left, 
right, or center).

SV
View

Position

Top

Left
Center
Right (default)

Bottom

Left
Center
Right

  

■ Concentrated monitoring zone: W (width) × H (height)

Set the unnecessary area to exclude from the monitoring zone.
• Default: W 0 m × H 0 m
• Setting range [m]: Each of W, H 0, 0.1, 0.2, 0.3

Monitoring zone
width (W)

Monitoring
zone height (H)

Concentrated monitoring
zone height (H)

Concentrated
monitoring zone

Concentrated
monitoring
zone width (W)

  

■ Monitoring zone: W (width) × H (height)

By setting the width and height, the monitoring zone of the rectangle can be set.
• Default: W 4.500 m × H 1.700 m
• Setting range: W 0.001 m × H 0.001 m ~ W 5.600 m × H 5.600 m

  

■ Teaching

The ability to pre-train field.
Objects whithin the monitoring zone are not detected while teaching.
• Re-teach when the environment has been changed or objects are added or removed 

in same area.

• Operate teaching in the environment free from snow, rain, fog, hail, or mutual 

interference of another laser scanner.

• For re-install the unit teaching already at no teaching required area, set the use of 

teaching data to OFF.

  

Minimum object size

Set the size of minimum detection object.
Even objects smaller than the set minimum detection object size can be detected 
depending on the environment.
• Default: 50 mm
• Setting range [mm]: OFF, 50, 80, 100, 150, 200, 250, 300, 350, 400

  

■ Monitoring time

If there is an object in the field during the set monitoring time, an obstacle detection 
output is ON.
By setting monitoring time longer, the laser scanner scans field repeatedly and scans 
obstacles without being affected by snow or rain. 
• Default: 100 ms
• Setting range [ms]: 0, 100, 200, 300, 400, 500, 600, 700, 800, 900

  

■ Visible laser activation

By operating the visible laser, the user can check the area the device is scanning for 30 
seconds.