Parameter 3

 group

 

Parameter

Display

Default

Setting range

Display

condition

P3-1

Lock

LOC

OFF

OFF : Unlock 

LOC.0 : Lock All

LOC.1 : Lock parameter 1 / 2 / 3

LOC.2 : Lock parameter 2 / 3

LOC.3 : Lock parameter 3

-

P3-2

Parameter

 

reset

mRST

ENA

ENA: enable, DISA: disable

-

  

Parameter 2

 group

 

Parameter

Display

Default

Setting range

Display

condition

P2-1

Decimal 

point 

position of 

display value

DOT

00000

00000, 0000.0, 000.00, 00.000, 0.0000

P1-1 Input 

operation 

mode: 

F1 to 2, 

F7 to 14 

P2-2

Time unit 

01)

tUNT

tSEC

T.SEC, T.MIN

P1-1 Input 

operation 

mode: 

F3 to 6 

P2-3

Time range

 

(unit: sec) 

01)

tSEC 99 (99 

999.99: 999.99 s

9999.9: 9999.9 s

99999: 99999 s

P2-4

Time range 

(unit: min) 

 01)

tMIN 99 (99 

999.99: 999.99 m

9999.9: 9999.9 m

99999: 99999 m

P2-5

Input A 

prescale

 

mantissa (x)

PScaH

^0000

0.0001 to 9.9999

P1-1 Input 

operation 

mode: 

F1 to 2, 

F4, 

F7 to 14

P2-6

Input A 

prescale

 

exponent (y)

PScaY

10   01

10 - 9 (10

-9

) to 10 09 (10

9

)

P2-7

Input B 

prescale

 

mantissa (x)

PScbH

^0000

0.0001 to 9.9999

P1-1 Input 

operation 

mode: 

F7 to 8 

P2-8

Input B 

prescale

 

exponent (y)

PScbY

10   01

10 - 9 (10

-9

) to 10 09 (10

9

)

P2-9

Display

 

cycle

dISpT

)05

OFF

 02)

 

or 0.05, 0.5, 1, 2, 4, 8 sec

P1-1 Input 

operation 

mode: 

F1 to 2, 

F7 to 8, F14 

P2-10

Input B 

setting value

 

(INB)

COUnB

99999

1 to 99999

P1-1 Input 

operation 

mode: F14

 01)  To enter P2-3 time range (unit: sec) and P2-4 time range (unit: min) setting, press [▲] key at P2-2 time unit. 
 02) Only available operation mode F2, F14

Parameter

Display

Default

Setting range

Display

condition

P1-1

Input 

op

e

ration 

mode

MODE

F1

F1 to F14

-

P1-2 Input A 

sensor type

IN-A

NPnhF

NPN.H.F : NPN non-contact input1

NPN.M.F : NPN non-contact input2

NPN.L.F : NPN contact input

PNP.H.F : PNP non-contact input1

PNP.M.F : PNP non-contact input2

PNP.L.F : PNP contact input

-

P1-3 Input B 

sensor type

IN-B

NPnhF

P1-1 Input 

op

e

ration 

mode:

F2, F6 to 12, 

F14 

 01)

P1-4 Output mode

OUT-T

STARD

[Relay double output model]

STARD : S (Standard)

OUT-H : H (High)

OUT-L : L (Low)

OUT-B : B (Block)

OUT-I : I (One-shot)

OUT-F : F (Deflection) *

P1-1 Input 

operation 

mode: 

except F11 

&

* P1-1 Input 

operation 

mode: 

except F14 

P1-5 Output 

hysteresis

HYS

0001

[Relay single / double output model]

0000 to 9999

•  Varies according to P2-1 Decimal point 

position of display value

P1-1 Input 

operation 

mode:

F1, F7 to 8

P1-6 Delay 

monitoring

GUARD

fDEFY

[Relay double output model]

F.DEFY: L comparative output limit *

STAR.T: Start compensation timer 

 02)

P1-1 Input 

operation 

mode: 

F1 to 10

*P1-4 Output 

mode: S, B, F

P1-7 Compensation 

time

STArT

)0

[Relay double output model]

0.0 to 99.9 sec

P1-6 Delay 

monitoring: 

STAR.T

P1-8

Input A 

auto-zero 

time

AUToA

999(9

0.1 to 9999.9 sec

P1-1 Input 

operation 

mode: F1, F4, 

 

F7 to 8

P1-9

Input B 

auto-zero 

time

AUToB

999(9

P1-1 Input 

operation 

mode: F7 to 8

P1-10 Memory 

retention

MEMO

OFF

OFF, ON

P1-1 Input 

operation 

mode: 

F11 to 14 

 01) In case of P1-1 Input operation mode F13, input B sensor type is not displayed and IN-B setting is same as IN-A.
 02)  [◀] key: Entering compensation time setting.

  

Parameter 1

 group

 

Output Mode

Output mode is available to set.  
The output modes supported by each model are different.

 

-  Indicator : not support output mode, Relay single output model: S (Standard), 

 

 Relay double output model: total output modes 

OFF:

ON:

H:

 

hysteresis

  

■ S (Standard) / B (Block) output mode

• Comparative value setting condition

 

S (Stanrdard): individual output operation regardless of size or order of set 
comparative values 

 

B (Block): L < H

H output:  Display value ≥  Comparative value

 H

L output:  Display value

≤ 

Comparative value L

H

L

H

L

H

H

Comp

ar

ative

 

value

Output

  

■ H (High) output mode

  

■ L (Low) output mode

• Comparative value setting condition: 

individual output operation regardless of 
size or order of set comparative values

• Comparative value setting condition: 

individual output operation regardless of 
size or order of set comparative values

H output:  Display value

≥ 

Comparative value

 H

L output:  Display value

≥ 

Comparative value L

H

L

H

L

H

H

Comp

ar

ative

 

value

Output

H output:  Display value

≤ 

Comparative value

 H

L output:  Display value

≤ 

Comparative value L

Comp

ar

ative

 

value

Output

H

L

H

L

H

H

  

■ I (One-shot) output mode

• Comparative value setting condition: individual output operation regardless of size or 

order of set comparative values

• 

One-shot output time: 0.3 sec (fixed)

• No hysteresis.

H output:  Display value

≥ 

Comparative value

 H

L output:  Display value

≥ 

Comparative value L

Comp

ar

ative

 

value

Output

H

L

H

L

0.3 s

0.3 s

  

■ F (Deflection) output mode

• 

Transmits outputs when the saved setting value exceeds H deviation or L deviation.

• Comparative value setting

 

:  Based on the set value, use the front HIGH / LOW set value thumbwheel switch to set 

the H / L deviation.

 

( The set deviation value is saved during Power OFF until it is re-set.)

• Comparative value setting range

 

: 0.0001 to 99999

 

The setting range is different according to the P2-1 Decimal point position of display 
value setting.

 

E.g.)  

In case of P2-1 Decimal point position of display value = 0000.0, 

 

setting range = 0.1 to 9999.9

• 

Saving setting value: [MODE] + [▲] 

• Checking setting value: [▲]

• 

The deviation can be set to “0” but the actual operation will be the same as “1”.

01)

02)

 (

Max.)H deviation

SV

(

Min.) L deviation

Power

Save SV

L deviation

output

deviation

output

Save SV

01) When P1-6 Delay monitoring = F.DEFY is set, there is no output.

02) The graph is assuming that there is a saved setting value prior to the setting value save point. The actual 

output position may be different.

Summary of Contents for MP5M Series

Page 1: ...ce panel to use Failure to follow this instruction may result in fire or electric shock 04 Do not connect repair or inspect the unit while connected to a power source Failure to follow this instruction may result in fire or electric shock 05 Check Connections before wiring Failure to follow this instruction may result in fire 06 Do not disassemble or modify the unit Failure to follow this instruct...

Page 2: ...range F S 0 01 rdg 1 digit F4 Passing time F5 Time interval F6 Time differential F7 Absolute ratio 0 0005 Hz to 50 kHz F S 0 05 rdg 1 digit F8 Density F9 Length measurement 1 0 to 99999 F10 Interval F11 Accumulation F12 Addition subtraction individual input 19999 to 99999 F13 Addition subtraction phase difference input F14 Length measurement 2 0 to 99999 Specifications Series MP5M N MP5M 1 MP5M 2 ...

Page 3: ... 9999 9 sec P1 1 Input operation mode F1 F4 F7 to 8 P1 9 Input B auto zero time AUToB 999 9 P1 1 Input operation mode F7 to 8 P1 10 Memory retention MEMO OFF OFF ON P1 1 Input operation mode F11 to 14 01 In case of P1 1 Input operation mode F13 input B sensor type is not displayed and IN B setting is same as IN A 02 key Entering compensation time setting Parameter 1 group OutputMode Output mode is...

Page 4: ...ault 999 99 m 9999 9 s 9999 9 m 99999 s 99999 m MP5 L Distance m Input A t1 t1 α t2 α t5 α t2 t3 α t6 α t3 t4 t5 t6 Hold Display F5 time interval Displays measured time of input A ON Time interval T t t measured time of input A ON sec Display value Display unit Time interval SEC MIN 999 99 s default 999 99 m 9999 9 s 9999 9 m 99999 s 99999 m Stamp Motor MP5 ta Return time 20 ms Input A t1 t1 t2 t2...

Page 5: ...d input A pulses and subtracted input B pulses When there are two inputs simultaneously it will not count Add Sub individual input A α input B α α prescale value of input A Display value Display unit Addition Subtraction individual Quantity EA Photoelectric sensor InputA add InputB sub MP5 Input A Input B RESET Display 0 0 1 2 2 2 2 3 1 1 3 α display value for 1 F13 addition subtraction phase diff...

Page 6: ...r than the interval of the slowest input signal If the setting time is too long and there is no input signal the rate at which the display value falls to 0 zero decrease and output response rate may slow down Prescale Displays values in required units or specific multiples by counting the number of input pulses then multiplying the number of pulses or the length of pulses by variables X 10y E g pr...

Reviews: