background image

2D-2

 Special considerations for the AutoPilot 

Combina-

tion

 Manifold

Under normal operation, a small amount of gas is introduced 
into the pool system by the injector. Plumb the Manifold so that 
these bubbles do not interfere with the operation of pool equip-
ment. For example:

1.

  Install the manifold after any Pressure Pool Cleaners (such 

as a Polaris 360).

2.

  Install the manifold after any Tablet/Erosion Feeders that 

could collect gas bubbles.

2D-3

. Water Check Valve:

If the pool equipment is mounted 

above the water line, a check valve must be installed between 
the pump outlet and the Injector Manifold.  This will prevent the 
pump from draining and losing its prime (when not in use).

2D-4

. Pressure Test:

 

If a pressure test is required, it should be performed prior to 
connecting the Ozone Gas Line.  A 3/4” pipe cap is provided 
for the pressure test.

2D-5.

 Ozone Gas Line - refer to Figure 2.

 

1.  

Install Tube Adapter on injector.  Use thread sealant if 

needed. (Do not use thread tape.)

2.

  Connect  the shorter end of the Ozone Check Valve and 

Tube Assembly with the check valve installed onto the 
Tube Adapter.

3.

  Cut off the excess tubing from the longer end so that the 

line from the injector to the CoPilot is as straight and free 
from dips and loops as possible.

4.  Install Clamps on the Tube Adaptor and on both ends of 

Check Valve.

Equipment

Ozone Check Valve

From Pool

Flowmeter

Tube Adapter

and Tube Assembly

to Pool

Return

Lug(s)

Bonding

Indicators

Ozone Power

Flow Control Assembly

(Install after checking flow)

(Preinstalled)

Check Valve

Clamps

3

Figure 2

 Installation Diagram

5.

  The base of the CoPilot has two tube connections. Con-

nect the longer end of the ozone supply tubing to the 
port marked "OZONE" (see Bottom View - Figure 3).

 

NOTE: Connecting the Ozone Line to the incorrect port 

will cause damage to the ozone generator.

SECTION 3 

Operation

Operation

3A General

To achieve optimal performance from the CoPilot system, the 
pool must be as clean as possible to start with.  Refer to the 
“Pool Water Preparation” section of your Pool Pilot manual.

3B Initial System Start-Up

Upon completing all of the system connections and cleaning 
the pool, you are ready to start the CoPilot.

1.

  Check electrical connections.

2

.  Check for proper voltage.

3.

  Turn on pool circulation system.

3C Normal Operation

1. 

Ozone Power

 

Indicator Lights: When the pool’s circulation 

system starts, the green LED indicator(s) on the front of 
the CoPilot will illuminate. The COP-A and COP-B should 
show 1 and 2 indicators, respectively.

2. 

Gas Flow: Connect the Flowmeter provided to the “AIR IN” 

port on the base of the CoPilot (see Figure 3). Under worst-
case system conditions the Flowmeter Ball should indicate 
at least a small amount of air fl ow. If not, adjust system 
valves as required to reduce back pressure and/or increase 
fl ow through the manifold. Under nominal conditions, the 
Ball should fl oat above the middle of the fl owmeter. It is ok 
if the Ball is all the way at the top if it is not stuck. Tap the 
Flowmeter to verify that the Ball is not stuck.

 

If you experience complications see TROUBLESHOOTING 

Section 4D. 

3D Flow Control Assembly

Once proper suction is established, remove the Flowmeter 
and install the Flow Control Assembly on the “AIR IN” port of 
the CoPilot. The Flow Control Assembly must remain attached 
to the CoPilot, except when temporarily removed to verify fl ow 
with the Flowmeter

3E  System Shut-Down

The following sequence of steps must be followed for servicing 
or for storage.

CoPilot  Corona Discharge Ozone Generators

Figure 3

 CoPilot Connections

Summary of Contents for CoPilot Ozonator 3

Page 1: ...Corona Discharge Ozone Generators INSTALLATION OPERATION MANUAL P N 4 1397 01 Rev G...

Page 2: ...No 8 AWG 8 4 mm2 solid bonding conductor between this point and any metal equipment metal enclosures of electrical equipment metal water pipes or conduit within five 5 feet 1 5m of the unit as needed...

Page 3: ...4 COP 2 B 1 2 THREADED CONDUIT COP B CE OPEN 18 3 CORD 44IN LONG 9 3 235 219 8 6 382 15 0 13 6 344 COP 1 A NEMA 5 15P 44IN LONG COP 2 A 1 2 THREADED CONDUIT COP A CE OPEN 18 3 CORD 44IN LONG 10 3 262...

Page 4: ...ion The CoPilot units are designed for wall mounting See Figure 1 Mount generator in a clean protected area either indoors or outdoors preferably out of direct sunlight Locate generator out of reach o...

Page 5: ...y tubing to the port marked OZONE see Bottom View Figure 3 NOTE Connecting the Ozone Line to the incorrect port will cause damage to the ozone generator SECTION 3 Operation Operation 3A General To ach...

Page 6: ...e CoPilot allow the unit to dry completely before restarting the unit Evidence of water in the CoPilot may void the warranty WARNING DoNOTtouchtheendsoftheOzoneCheckValve and Tube Assembly or check va...

Page 7: ...bly is Clogged Clean or replace flow control assembly 4D 5 Symptom Ozone tubing becomes yellow brown and brittle a The high concentration of ozone created by the CoPi lot family of corona discharge oz...

Page 8: ...CE 9 0789 04 Transformer Indicator Board COP 1 A COP 2 A COP A CE 9 0789 05 Transformer Ozone Power Supply COP 2 B COP B CE 9 0789 06 Check Valve and Tube Assembly All CoPilot Models 9 0789 072 Fuse...

Reviews: