WARNING
Only the supplied or technically identical connectors may be used on the termi-
nals blocks for the AC supply and the relay outputs (→ 9 Technical data).
To ensure protection rating IP 20 for the housing and the terminals, fully tighten
the screws of the unused connector contacts�
WARNING
Do not use unconnected terminals which are not shown in the drawing such as
terminal 11 as support point terminal�
6.3 Voltage supply (power)
► Voltage supply see type label�
► Connect the device to terminals 21/22 (L) and 23/24 (N)�
► Lay all supply and signal cables separately� Use a screened cable if required in
the application�
6.3.1 AC supply
WARNING
The AC supply cable must be protected according to the cross-section used
(max� 10 A)�
The low voltage provided for the sensor supply meets the SELV criteria according
to EN 61010, overvoltage category II, soiling degree 2�