15
6.1.2 Device-specific information
You will find the IODDs necessary for the configuration of the IO-Link unit and
detailed information about process data structure, diagnostic information and
parameter addresses at www�autosen�com�
6.1.3 Parameter setting tools
You will find all necessary information about the required IO-Link hardware and
software at www�autosen�com�
7 Parameter setting
Using an IO-Link capable parameter setting tool, the following options are availa-
ble:
- Reading current process values�
- Reading, changing and saving current parameter settings and transmitting
them to other units of the same type�
► Connect the unit via the IO-Link interface to a PC or PLC with suitable parame-
ter setting software�
7.1 Adjustable parameters
OU
Output function
Analogue output signal:
[I]:
4���20 mA
[Ineg]: 20���4 mA
ASP
Analogue start point
for temperature
With setting [OU] = [I]:
Measured value at which the output signal is 4 mA�
With setting [OU] = [Ineg]:
Measured value at which the output signal is 20 mA�
AEP
Analogue end point
for temperature
With setting [OU] = [I]:
Measured value at which the output signal is 20 mA�
With setting [OU] = [Ineg]:
Measured value at which the output signal is 4 mA�
Minimum distance between ASP and AEP = 5 °C or 9 °F�
COF
Zero-point cali-
bration
Setting range: ± 10 K in steps of 0�1 K� The internal
measured value "0" is shifted by this value�
UK
Summary of Contents for AT001
Page 9: ...9 DE ...