Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 26
Procedure for System Commissioning Using the
Aperture
1. Align the AutroPath HC800 system using the
Basic Alignment procedure. At the completion of
this alignment, the output signal at the receiver
may indicate a fault condition as a result of signal
saturation.
2. Attach the aperture to the front of the AutroPath HC800
transmitter
module using the captive screws provided.
For best weather protection, the aperture hole should be
located at the top of the unit.
3. Perform a zero calibration. After performing the zero
calibration, the receiver module should display a normal
condition (green LED) and a steady 4 mA output.
NoTe
If the receiver continues to indicate a fault
condition as a result of signal saturation, rotate
the aperture 90 degrees and repeat step 3 above.
ReCommeNDAtIoNS FoR uSING tHe HARt FIeLD
CommuNICAtoR
WarnInG
The AutroPath HC800 does not use Intrinsically Safe
circuitry for connection to the HART 475 Communicator.
Connecting a HART 475 Communicator to the
AutroPath HC800 may invalidate the Intrinsic Safety
circuits of the HART 475 Communicator.
• The HART communication device must include the
AutroPath HC800 device descriptor (DD) software
menu. The use of HART communication devices
without the proper DDs may establish generic mode
HART communication, but will not enable proper
operation with AutroPath HC800. Refer to the HART
Appendix for additional information.
• A minimum level of understanding with regard to the
operation and navigation of the HART communicator
is required. Please refer to the appropriate HART
communicator instruction manual for basic operating
instructions if required. Additional information on the
use of the HART communicator is provided within the
HART Appendix in this document.
• For proper HART communication to occur, it is required
that a 250-500 ohm resistive load be present in the
AutroPath HC800 analog 4–20 mA signal loop output.
See “Wiring Procedure” in the “Installation” section.
GAIn LeVeL CHeCK (
optional
)
It is necessary to complete the alignment procedure
before checking the gain level. HART or Modbus
communication is required to check the gain.
Procedure
1. Connect the handheld HART communicator to the
receiver module’s 4–20 mA circuit.
2. Turn on the HART communicator and check for
AutroPath HC800 device recognition. When HART
communication is established, the AutroPath
HC800 Online menu will be displayed on the com-
municator display.
3. From the Online menu, navigate to the Detector
Setup menu, then select the Sensor Setup menu.
4. The following screen will be displayed. Observe
the level indicated for “Gain.”
Sensor Setup
1) Processing mode
xxxx
2) Interconnect mode
xxxx
3) Log interim beam block Y/N
4) Gain Mode
xxxx
5) Gain
xx
6) Tx lamp voltage
xxxx
7) Auto voltage during cal
E/D
8) Beam block fault time
xxx
Gas Gain number
5. Table 8 can be used as a guideline for new instal-
lations to assess the detector gain level with
proper alignment.
Distance
Transmitter Type
Short Range
Long Range
5
1 (aperture)
20
5 (aperture)
30
1
2 (aperture)
40
2-5
5 (aperture)
60
5-10
1-2
80
2-5
100
2-5
120
5-10
table 8—Expected Gas Gain Settings for autropath Hc800