Internal Cable Connections
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE,
Rev. J, 2011-12-06,
Autronica Fire and Security AS
Power Supply
Protective Earth
In the fixed mains wiring to the panel a
two-pole disconnect device must be
provided to disconnect the equipment
from the power supply when servicing
is required. Normally, this switch is a
two-pole automatic fuse located in the
fuse terminal box at the premises. This
fuse location must be marked "Fire
Alarm System".
!
The isolation of the mains wiring must
be of either:
inflammability class V2
or
the wiring has to be fixed to the
cabinet separated from all other
cables.