Service and Maintenance
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE,
Rev. J, 2011-12-06,
Autronica Fire and Security AS
7. Service and Maintenance
7.1 Introduction
The AutroSafe Interactive Fire Alarm System provides a Log Menu,
which records all system events, i.e. fire alarms, prealarms, faults,
restorations/disablements, user operations and tests.
The owner of the system / authorized personnel has a duty to register
all events in a Control Journal.
7.2 Monthly Maintenance
Step
Description
1
Look through the log journal to find any possible irregularities.
2
Make sure that possible changes in the building structure or storage environment have not
affected the detectors’ capability to detect a potential fire.
3
Make sure that the detectors are not covered with paint or contaminated with dust or dirt.
4
Perform a visual inspection of the Fire Alarm Control Panel.
5
Perform a simple test of display and panel functions
6
Test the sounders.
7.3 Annual Service and Maintenance
IMPORTANT
To ensure optimal reliability and stability of system operation
and performance, a system restart shall always be carried out at
least once a year at each annual system service.
We also recommend that the system is restarted if the system
enters System Fault Condition (according to standard
procedures).
For SIL2 approved systems, service and maintenance shall
be carried out according to the proof test interval in
chapter 4; Reliability Accessments in RAMS report 2053
Rev A.