6.5 Testing Loop Outputs
This chapter describes how to test each Loop Outputs individually.
When the test is initiated for a selected loop output, a test signal will
be sent to this output.
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
Scroll down to Loop Outputs, then press Enter.
Use the arrow button to select the Loop Output that
is to be tested.
(To view detailed information for the selected loop output before
testing, you can press Enter, then return to the previous level by
pressing the Cancel button
).
Press the Function button
To start the test, press Enter.
Press Enter once more to confirm.
To stop the test, use the arrow up/down button to select the loop
output that is set to test mode, press the Function button
,
use the arrow down button to select Stop Test, then press Enter
twice.
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is
to be tested.