Configuration Examples
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 125
9.2.8 Step 2: Connect the new Detection Zones to the Alarm Zone
From the Points menu, perform the following:
Press the back/cancel button to move back one level to
Unit
Configuration
.
Use the arrow up button to scroll upwards to
Detection Zones,
then press Enter.
As all Detection Zones (DZ1, DZ2, DZ3 and DZ4) are to be
connected to the Alarm Zone in this example, use the multiselect
feature* to select
all
four Detection Zones.
* To select all four Detection Zones at the same time, press and
hold down the Select button
to mark the first Detection Zone
DZ1, then while still holding down the Select button, press the
Arrow Down button to select the second, third and fourth (DZ2,
DZ3 and DZ4).
Press the Function button
Press Enter to select the uppermost menu selection
Connect to
Alarm Zone.
Press Enter to connect all four Detection Zones to this
Alarm Zone.
Press Enter to confirm the settings (
Accept
).
9.2.9 Step 3: Save Configuration / Restart System
Refer to chapter 9.2.4.