System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 16
3.4 Day Mode Operation Times
By default the entire system is set to Night Mode, meaning that the
system is set to immediate output actioning.
The system menu
Day Mode Operation Times
allows you to
configure settings for automatic delay of the activation of outputs to
Fire Alarm Devices (FAD) and/or Fire Alarm Routing Equipment
(FARE) at certain periods.
The settings will only affect points that have been set to “Override
Delay and Dependency NO” in detection zones configured as
Delayed Action Detection Zones or Delayed Dependency Detection
Zones.
To achieve this, you simply choose the days in the week when you
want the system to automatically enable the delays, plus the exact
duration of the disablement in hours and minutes (the start time and
end time).
A maximum of 14 settings are available (for example, 7 days; 2
intervals per day, or, for example, 14 intervals for one specific day).
Note that overlapping settings are not possible.
From the Service Menu, perform the following:
Press Enter to select System Settings.
Press the arrow down button to select Day Mode Operation
Times, then press Enter twice.
Use the left/right arrow button to select among the following days:
o
Unspecified
o
Every day
o
Monday to Friday
o
Saturday, Friday, Thursday, Wednesday, Tuesday, Monday,
Sunday.
Press Enter.
Use the alphanumeric keypad to specify the start time*
(hours:minutes), then press Enter.
Specify the end time* (hours:minutes), then press Enter.
* Note that if an invalid input is given, a message indicating this will
appear in the display.
It is recommended that all settings (for example, settings for 4
different days) are done before the settings finally are confirmed.
To view existing Day Mode Operation Times, refer to chapter 3.4.1.
To add new Day Mode Operation Times to existing ones at a later
point of time, refer to chapter 3.4.2.
Press and hold down the Function button
a few seconds
(“Long press to accept or cancel”).
To confirm the new settings (Accept), press Enter.