System Settings
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 23
To confirm the new settings, press Enter once more.
3.11 Detection Zone (DZ) Global Dependency
This menu selection allows you to turn on Detection Zone Global
Dependency, meaning that an alarm in a detecion zone will require a
second alarm from another point, in any detection zone, before the
detection zone activates any output.
A fire alarm signal from a
single
detector
will initiate
no
actions, i.e.
there will be no
actioning of outputs
to;
Fire Alarm Devices (FAD)
Fire Alarm Routing Equipment (FARE)
Fire Protection Equipment (FPE)
From the Service Menu, perform the following:
Press Enter to select System Settings.
Press the arrow down button to select DZ Global Dependency,
then press Enter.
The following message appears:
“If enabled, an alarm in a DZ will require alarm from another point, in
any DZ, before the DZ activates any output. Turn on DZ Global
Dependency?”
To answer YES, press Enter, then press the right arrow button,
and press Enter once more.
To confirm the new setting, press Enter once more.
3.12 Battery Parameters
This menu allows you to specify the following:
the minimum charge voltage
the battery low voltage limit
the maximum charge current
the maximum resistance limit
From the Service Menu, perform the following:
Press Enter to select System Settings.
Press the arrow down button to select Battery Parameters, then
press Enter twice.
Press the right arrow button to select the minimum charge voltage
(default 21000mV, minimum 20000mV, maximum: 31000mV),
then press Enter.
Press the right arrow button to select the battery low voltage limit
(default 21000mV, minimum 17900mV, maximum: 31000mV),
then press Enter.
Press the right arrow button to select the maximum charge
current (default 1500mA, minimum 1000mA, maximum: 2000mA),
then press Enter.
Press the right arrow button to select the maximum resistance
limit
(default 800mOhm, minimum 200mOhm, maximum: 5000
mOhm), then press Enter.
To confirm the new setting, press Enter once more.