5.2.12 Disconnect from Panel
This menu allows you to disconnect a detection zone from a
“Larmlagring” Panel. Note that the menu selection is available only if
a such panel is connected to the system.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Disconnect from
Panel, then press Enter twice.
Use the arrow down/up button to select the panel to be
disconnected, then press Enter.
To confirm the setting, press Enter once more.
5.2.13 Show Member Points
This menu allows you to view a list of all points belonging to a
selected detection zone.
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Show Member
Points, then press Enter.
To view detailed information for a selected point, use the arrow
down/up button to select the point, then press Enter.
The following information will appear:
o
the point’s name/type
o
information on whether the point is set to override delay and
dependency or not (YES/NO)
o
the point’s performance class day settings
o
the point’s operation class day
settings
o
the point’s performance class night settings
o
the point’s operation class night settings
5.2.14 Show Connected Units
This menu allows you to view all connections related to a selected
detection zone, i.e. what the detection zone activates (for example,
alarm zone, outputs, etc.).
From the Detection Zones Menu (5.2.1), perform the following:
After pressing the Function button for the selected detection
zone(s), use the arrow down button to select Show Connected
Units, then press Enter.
To view detailed information (name, parent alarm zone and
immediate activation status) for all connections related to a
selected detection zone, use the arrow down/up button to select
an alarm zone, then press Enter.