Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 70
5.8.2 Configure Properties for a Loop Input
The following properties can be changed:
the name of the loop input
supervisory (Yes/No);
If Yes is selected, the inputs that are defined for technical alarms
will be activated during normal operation, meaning that an
indication of an event will appear in the display (supervisory text)
on the activation of the loop input. The panel will be in
Supervisory Condition.
From the Loop Inputs Menu (5.8.1), perform the following:
After selecting the Loop Input in question by means of the
arrow down/up buttons, press Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter.
Use the left/right arrow buttons to select Supervisory:Yes or No,
then press Enter.
To confirm the setting, press Enter once more.
Summary of Contents for Autroprime 2
Page 148: ......