Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 76
5.9.6 Disconnect from Alarm Zone
This menu allows you to disconnect a selected local input from an
alarm zone.
From the Local Inputs Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to
Disconnect from Alarm Zone, then press Enter.
In the display you will now see a list of all alarm zones that are
connected to the selected local input.
To disconnect the selected local input from an alarm zone, use
the arrow down button to select the alarm zone, then press
Enter.
To confirm the setting, press Enter once more.
5.9.7 Show Connected Units
This menu allows you to view all connections that are connected to
the selected local input.
From the Local Input Menu (5.9.1), perform the following:
After pressing the Function button for the selected local input(s),
use the arrow down button to scroll downwards to
Show Connected Units, then press Enter.
In the display you will now see a list of all connections that are
connected to the selected local input.
Use the arrow up/down button to select a connection, then press
Enter.
In the display you will now see the name and unit function of the
connections that are connected to the selected local input.