Interfacing Voyage Data Recorder 

Systems 

 

AutroSafe VDR Interface BSL-336 

 

 

 
 
 
 

   Protecting life, environment and property...

       

 

 

116-P-BSL336/EE, RevA 2007-01-25 

 

Summary of Contents for AutroSafe Self Verify BSL-336

Page 1: ...Interfacing Voyage Data Recorder Systems AutroSafe VDR Interface BSL 336 Protecting life environment and property 116 P BSL336 EE RevA 2007 01 25...

Page 2: ...ty for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire and Se...

Page 3: ...l Communication Board 9 3 4 1 Jumper Settings EAU 321 10 3 4 2 Termination by use of ribbon cable and standard screw terminal block 11 3 4 3 Termination by use of cable XBA 055 12 4 BSL_336 Installati...

Page 4: ...2 6 6 CfgBaud Set Baud Rates 22 6 7 CfgPeriod Set Reporting Periods 23 6 8 CfgTalker Set Talker Identification 23 7 Testing BSL_336 24 7 1 dm0x10 Trace AutroCom and VDR Messages 24 7 2 DoAlive Send Al...

Page 5: ...ocumentation 116 P BSL336 CE Datasheet 1 3 IEC Standard requirements According to ISO6112 1 the manual is required to contain the following information a Identification of lines A and B Re chapter 4 2...

Page 6: ...ace is in compliance with IEC 61162 1 and IEC 61162 2 First edition 1998 09 Maritime Navigation and Radio Communication Equipment and Systems Second edition 2000 7 IEC PAS 61162 102 Extra Requirements...

Page 7: ...232 RS 422 AutroSafe communication Port 1 19200 baud 8 N 1 RS 232 Service computer Service port 115200 baud 8 N 1 RS 232 Cable Terminals Screw connection maximum 2 5mm2 cable Interface Options Port 0...

Page 8: ...Red Pulsating Fault The reason for the fault will normally be presented on the AutroSafe display as a fault from BSD 336 The Fault LED will also flash if the AutroSafe communication is lost ST0 Yellow...

Page 9: ...RS 232 Service Port 6 NC 22 RX RS 232 Service Port 7 NC 23 RS 232 Signal Reference Service Port 8 NC 24 NC 9 NC 25 TX RS 232 Port 0 10 NC 26 RX RS 232 Port 0 11 NC 27 Signal Reference Port 0 12 NC 28...

Page 10: ...r 3 3 1 3 2 Requirements Service computer to run software BSL 336 software CD contains AutroCom test software and documentation Relevant test cables to connect service computer to BSL 336 o XJA 029 co...

Page 11: ...ate with BSL 336 using RS 232 on port 1 or 2 The EAU 321 Serial Port Communications Board when installed is located as per figure Communications boards LON Interface board EAU 310 if installed Serial...

Page 12: ...e 10 3 4 1 Jumper Settings EAU 321 Note that J5 determines port 1 and J6 determines port 2 in an application where port 1 is in use by other equipment then J6 should be set as shown in the diagram to...

Page 13: ...and 2 2 4 20 1 3 19 5 Tx 9 GND 3 Rx Terminal Block The drawing shows an EAU 321 Port 1 connection EAU 321 Port 2 may be used with connection terminals 13 15 and 19 Interfacing Voyage Data Recorder Sy...

Page 14: ...EAU 321 Port 1 Port 1 13 14 15 Tx Rx GND RS 232 1 20 Port 2 3 Rx 5 Tx 9 Cable XBA 055 BSL 336 Cross section of EAU 321 XBA 055 Note Use the upper row of connection pins on the EAU 321 Interfacing Voya...

Page 15: ...24V DC power supply 4 1 2 Panel External Installation The module can also be placed on an external DIN rail and powered from AutroSafe or with an external 24V DC power supply Connect the unit to the r...

Page 16: ...y be damaged BSL 336 and EAU 321 must be connected to the AutroSafe power supply in the way described in the following figure 4 2 2 Connection with EAU 321 connection block Interfacing Voyage Data Rec...

Page 17: ...stallation 4 2 3 Connection with EAU 321 and cable XBA 055 Interfacing Voyage Data Recorder Systems AutroSafe Interactive Fire Alarm System 116 P BSL336 EE RevA 2007 01 25 Autronica Fire and Security...

Page 18: ...g AutroComPassWord Local password 9999 Description Enter if required Local Mode Report Report as communication fault Serial port on card Serial port used on EAU 321 for BSL 336 connectivity Baud rate...

Page 19: ...limited to 44 characters Obviously if a point tag and detection zone name are filled to their maximum number of characters some information may be lost in the string transmitted to the VDR unit it is...

Page 20: ...fe is Swedish a 0x61 In addition semicolon is a reserved character in AutroCom and must be avoided in AutroSafe name texts 5 3 AutroSafe Configuration The following sections detail configuration detai...

Page 21: ...hat the NMEA strings transmitted by the BSL 336 unit are understood and managed by the particular VDR in question 5 4 2 VDR Baud Rate Additionally the VDR supplier should supply a baud rate for transm...

Page 22: ...5 ON Rotary switch 0 6 2 Service Computer Based Configuration The BSL 336 has very few configurable settings The simplest way to modify the configuration is to connect a service computer to the BSL 33...

Page 23: ...e on port 1 19200 and port 0 38400 Note that the command is followed by the first parameter with no space in between The parameter separator is colon 6 3 2 List of commands Type help to get a list of...

Page 24: ...n EEPROM addr 0x21 with 30 many burn lines 14 04 30 818 NvRAM_Driv00 st02 Finished burning EEPROM If you change the baud rate the BSL 336 software must be restarted this can be done by typing the comm...

Page 25: ...2 hours Do not set the value to be shorter than 5 minutes as full status in a fire situation generates much traffic The command CfgPeriod4 120 sets default periods Interfacing Voyage Data Recorder Sys...

Page 26: ...TEST DZ1 Name 12 24 55 208 NMEA_Formt00 st02 FRFIR E 122455 FD PT 000 001 A V Fire Alarm TEST PT1 Name TEST DZ1 Name 7E To terminate trace type dm0 Do not leave an installation with trace active it s...

Page 27: ...VDR log Note that the periodic timer is re started so the next automatic system status will appear 120 configurable minutes later DoStatus It will print a line on the screen or many if the VDR trace...

Page 28: ...r event none X X EVE Operator events General faults Periodic status none X X none X X none X X X ALA System fault event none X X 8 1 1 Talker Identifier All strings from the fire detection system are...

Page 29: ...ext table for a complete list PT in the example 5 xxx Division indicator 2 UnitId Number MSD Formatted as three numeric characters The two most significant digits 12 in the example with a leading zero...

Page 30: ...00 FD PT 000 007 A V Fire PreAlarm TEST PT7 Name TEST DZ2 Name 1D FRFIR E 103002 FD PT 000 007 A V Fire Alarm TEST PT7 Name TEST DZ2 Name 78 FREVE 103002 DZ00002 Fire Alarm On TEST DZ2 Name 0F FREVE 1...

Page 31: ...larm state fault 7 a Alarm s ACK state V Not acknowledged 8 c c Alarm s description text The description text tells if this is fault or OK Example FRALA 143935 FR OT 00 901 H V Syst Fault AutroSafe co...

Page 32: ...s aa aa xxx xxx a a c c Field no Data form Field name Definition 0 FRDOR Header 1 a Message type E Event 2 hhmmss Event time The time is based on the AutroSafe timestamp of the event For periodic stat...

Page 33: ...Closed TEST FPA Name 6D Explanation of the Description Text Description text Door position Activated by AutroSafe Comment Door Open Open Not Activated Door Trans NA In transition Not Activated Door Cl...

Page 34: ...tate can be configured to depend on several detectors coincidence and or operator started delays A DZ event EVE will occur immediately after a detector point event FIR The DZ event will explain why a...

Page 35: ...TEST DZ20B Name 09 FREVE 000001 DZ00524 Fire AlACK S2 TEST DZ20C Name 0B Fault reports AutroSafe reports faults using two parameters Class and Reason the VDR log shows numeric values for both of these...

Page 36: ...s 5E FREVE 233006 FP00010 Unit FaultACK TEST FPA Name C 0 TEST Reason Details 37 FREVE 233006 FP00010 Unit FaultOK TEST FPA Name C 0 TEST Reason Details 5A FREVE 233006 FP00010 Unit FaultOKn TEST FPA...

Page 37: ...OP_EqStatusMsg Outp Unknown Unknown State unknown due to Disablement or Fault Operator Action Event When an operator affects changes on the fire alarm panel the BSL 336 will not be informed directly...

Page 38: ...that the information is relayed to fire safety personnel Description text Comment Unit Disabled Unit passive Unit Enabled Unit active normal Zone Disabled Zone passive Zone Enabled Zone active normal...

Page 39: ...and 8 to show detector alarm status Field no Data form Field name Definition FRFIR 0 Header 1 a Message type E Event Fire Alarm F Fault D Disablement 2 hhmmss Event time The time is based on the Autr...

Page 40: ...s if the detector is non normal Field 3 Detector types The detector types defined for AutroSafe 3 5 have been mapped to the following codes If it s important to know the exact type of detector use the...

Page 41: ...F 112600 FD PT 000 007 X Fire FaultACK TEST PT7 Name 9 1 TEST Reaso 09 FRFIR F 112600 FD PT 000 007 X Fire FaultOK TEST PT7 Name 9 1 TEST Reaso 64 FRFIR F 112600 FD PT 000 007 X Fire FaultOKn TEST PT7...

Page 42: ...IR D 143509 FD PT 000 001 X Fire Disabled TEST PT1 Name TEST DZ1 Name 7C FREVE 143504 FP00001 Outp On TEST FP1 Name 7D FREVE 143639 Sm00003 System status FINISHED 4D Communication fault repair FREVE 1...

Page 43: ...Fire Alarm System 116 P BSL336 EE RevA 2007 01 25 Autronica Fire and Security AS Page 41 BSL 336 Port 0 RS 232 1 2 3 4 5 TX RX GND RX TX GND 25 26 27 9 pin plug to service computer Remove the connecto...

Page 44: ...ogue open Select Bits per second 38400 Is VDR baud rate 4800 Once a connection with BSL 336 is established the HyperTerminal will display any data transmitted by BSL 336 To ensure that the connection...

Page 45: ...t from BSL 336 has been ascertained it is desirable that the final setup with VDR in place be tested for this to occur it is necessary that the VDR system allows such a test function See relevant VDR...

Page 46: ......

Page 47: ...Security AS 9 Reader s Comments Please help us to improve the quality of our documentation by returning your comments on this manual Title Interfacing Voyage Data Recorder Systems AutroSafe Interactiv...

Page 48: ...ronica Fire and Security AS Suggestions for improvements Thank you We will investigate your comments promptly Would you like a written reply Yes No Name Title Company Address Telephone Fax Date Please...

Page 49: ......

Page 50: ...conforms to the Quality System Standard NS EN ISO 9001 and is valid for the following product and service ranges marketing sales design development manufacturing installation and servicing of Fire det...