Log Strings
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 34
The hexadecimal numbers found between the "name" and the
"reason" texts are class and reason codes, both terminated by
semicolons.
$FREVE,112600,DZ00002,Zone Fault : TEST DZ2 Name 9;F; TEST Reason Details*3A
$FREVE,112600,DZ00002,Zone FaultACK: TEST DZ2 Name 9;F; TEST Reason Details*53
$FREVE,112600,DZ00002,Zone FaultOK : TEST DZ2 Name 9;F; TEST Reason Details*3E
$FREVE,112600,DZ00002,Zone FaultOKn: TEST DZ2 Name 9;F; TEST Reason Details*70
$FREVE,233006,FP00010,Unit Fault : TEST FPA Name C;0; TEST Reason Details*5E
$FREVE,233006,FP00010,Unit FaultACK: TEST FPA Name C;0; TEST Reason Details*37
$FREVE,233006,FP00010,Unit FaultOK : TEST FPA Name C;0; TEST Reason Details*5A
$FREVE,233006,FP00010,Unit FaultOKn: TEST FPA Name C;0; TEST Reason Details*14
Alarm-Zone Events
An alarm zone is a group of bells and sounders. Alarm zones are
activated when detectors report alarm.
Description text
Functionality
Comment
Zone Alert :
Bells ringing – warning pattern
There is a fire in a neighbour zone
Zone Evacuate:
Bells ringing – alarm pattern
There is a fire in this zone
Zone Silenced:
Bells silent – operator SILENCE
May be re-sounded
Zone Off :
Bells silent – operator RESET
System in quiescent
$FREVE,103002,AZ00003,Zone Alert : TEST AZ3 Name*35
$FREVE,103002,AZ00003,Zone Evacuate: TEST AZ3 Name*6F
$FREVE,103002,AZ00003,Zone Silenced: TEST AZ3 Name*64
$FREVE,103002,AZ00003,Zone Off : TEST AZ3 Name*34