PAGE 11
NOTE: FOR STANDARD OR CORNER INSTALLATION, STANDARD INSTALLATION SHOWN.
The exhaust vent termination on either vertical or horizontal installations shall be located as follows:
•
A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.
•
A minimum of 2 feet (610 mm) from any adjacent building.
•
A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.
•
A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.
VERTICAL EXTERIOR FLUE SYSTEM
FIGURE 5
PELLET VENT
▲
▲
6" MIN.
(152mm)
OPTIONAL