12 Stove
Installation
(for qualified installers only)
© Travis Industries
100-01252_000
4101004
Chimney Termination Requirements
•
Must have an approved cap (to prevent water from entering)
•
Must not be located where it will become plugged by snow or other material
•
Must terminate at least 3' above the roof
and
at least 2' above any portion of the roof within 10' (see
Figure 5)
Slanted Roofs
Flat Roofs
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Figure 5
Outside Air Requirements
•
Required for mobile homes & in certain localities (check with local building official)
•
Must not be drawn from an enclosed space (garage, unventilated crawl space)
•
Requires the outside air kit (sku 99200139 – see “a” below). The outside air kit attaches to the
bottom of the stove (see “c” below).
•
Outside air duct must have a rodent screen and rain hood (“b”).
•
NOTE: Make sure the center divider under the stove is in the farthest forward position (see page 7).
a
b
Back of Stove
c
Figure 6