Specifications
65
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
Model 5000/6000 BDM Ratings with a Model 4500 UPS
BDM Model
Input Utility
Voltage and
Selected UPS
Output Voltage
Input
Current
Output Voltage and
Maximum Current
Maximum
Output
Apparent
Power**
208/240:120/208
Hardwired
220 Vac
(60 Hz only)
24A
127/220 Vac (60 Hz only),
30.0/25.0A
4125 VA
208 Vac
24A
120/208 Vac,
30.0/25.0A
3900 VA
208/240:120/208
Hardwired
200 - 240 Vac
25A
100 - 120/200 - 240 Vac,
30.0/25.0A
3750 VA @ 200V
4125 VA @ 220V
4300 VA @ 230V
4500 VA @ 240V
208/240 120 L5 30R
208 Vac
24A
120 Vac,
43.3A*
3900 VA
208/240:120 L5-30R
200 - 240 Vac
24A
100 - 120 Vac,
48.3A*
4500 VA @ 120V
4500 VA @ 240V
208:120/208 L6-20R
208 Vac
24A
120/208 Vac,
15.0/20.0A
3900 VA
208:120/208 L6-30R
208 Vac
24A
120/208 Vac,
15.0/25.0A
3900 VA
208/240 120/240 L14 30R
208 Vac
24A
120/240 Vac,
15.0/21.1A
3900 VA
208/240:120/240 L14-30R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/24.7A
4500 VA @ 120V
4500 VA @ 240V
240:120/240E Hardwired
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
30.0/25.0A
European IT Neutral
4500 VA @ 120V
4500 VA @ 240V
240:120/240 L6-20R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/20.0A
4500 VA @ 120V
4500 VA @ 240V
240:120/240 L6-30R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/24.7A
4500 VA @ 120V
4500 VA @ 240V
*Total of currents in all available 100 - 120V output connections.
**Ratings based on 4000W load on BDM, plus sufficient linear inductive load to achieve the current rating of the input
plug, not to exceed the real-power or apparent-power rating of the PPU.
N
N
N
NO
O
O
OT
T
T
TE
E
E
E
Input and output currents are approximately the same when load is powered through bypass.
Summary of Contents for 4500 VA