SPECIFICATIONS
Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual
S
164201770 Rev 1
40
Table 4. Battery
Internal Batteries
EBMs
Configuration
700–1000 VA models: 36 Vdc (3 12V, 9 Ah)
1500 VA models: 48 Vdc (4 12V, 9 Ah)
3000 VA models: 72 Vdc (6 12V, 9 Ah)
1000 VA models: 36 Vdc (2x3 12V, 9 Ah)
1500 VA models: 48 Vdc (2x4 12V, 9 Ah)
3000 VA models: 72 Vdc (2x6 12V, 9 Ah)
Fuses
Not applicable
(4) 30A/125 Vdc fuses per EBM
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
Internal batteries: 3 hours
1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours
Battery Port
External three-pole Anderson connector on UPS for connection to EBM