Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual
S
164201770 Rev 1
1
Chapter 1
Introduction
The Extended Battery Module (EBM) can be added to the Avaya
®
9130
uninterruptible power system (UPS) to extend the available battery time
(see Table 1). Up to four EBMs can be installed with the UPS.
Table 1. Battery Runtimes (in Minutes) at 100% Load
Model
Internal Batteries
+ 1 EBM
+ 2 EBMs
+ 3 EBMs
+ 4 EBMs
1000 VA, 120V
5
30
55
83
108
1000 VA, 208/230/240V
7
29
51
81
98
1500 VA, 120V
5
23
48
67
91
1500 VA, 208/230/240V
5
24
44
72
89
3000 VA, 120V
3
20
36
53
71
3000 VA, 208/230/240V
3
18
34
53
69
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.