OPERATION
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
35
Table 2 shows the basic menu structure.
Table 2. Menu Map for Display Functions
Main Menu
Submenu
Display Information or Menu Function
UPS Status
Main status (mode and load) / Notice or Alarm status (if any) /
Battery status (state and charge level)
Event Log
Displays up to 127 events and alarms
The Event Log is also available through the serial port. See
“Retrieving the Event Log” on page 43.
Measurements
Load W VA / Load A pf / Output V Hz / Input V Hz / Bypass V Hz /
Input Line Events / Battery V min
Control
Go to Bypass
Transfers the UPS system to internal Bypass mode
When this command is active, the option changes to “Go to
Normal.”
Start Battery Test
Starts a manual battery test
See “Running Battery Tests” on page 47.
Reset Error State
Clears a “Battery Test Failed” alarm
Load Segments
Load segment 1: ON | OFF
Load segment 2: ON | OFF
These commands overrule user settings for load segments. See
“Configuring Load Segments” on page 45.
Restore Factory
Settings
Returns all settings to original values
Identification
UPS Type / Part Number / Serial Number / Firmware
Settings
User Settings
See Table 3 for details.
Service Settings
For administrative purposes only. This menu is
password-protected.