OPERATION
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
37
Table 3. User Settings (continued)
Default Setting
Available Settings
Description
Frequency Converter
[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.
Disabled
Overload Alarm Level
[10%] [20%] [30%] . . . [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.
100%
Generates the Output Overload
alarm at the set level.
Transfer to Bypass When Overload*
[Immediate] [After Delay]
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 15 on page 72.
Immediate
Power Strategy
[Normal] [High Efficiency]
See “Setting Power Strategy” on page 43.
Normal
Automatic Start Delay
[Disabled] [No Delay] [1s] [2s] . . . [32767s]
If Disabled, automatic restart is not allowed.
See “Configuring Load Segments” on page 45.
Load Segment 1: No Delay
Load Segment 2: No Delay
Automatic on Battery Shutdown
[Disabled] [No Delay] [1s] [2s] . . . [32767s]
Shutdown cancels if utility returns before the
delay expires. See “Configuring Load
Segments” on page 45.
Load Segment 1: Disabled
Load Segment 2: Disabled
Start on Battery
NOTE Utility must be present and
output enabled at initial UPS startup.
[Enabled] [Disabled]
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.
Enabled
Energy Saving Mode
[Disabled] [50W] [100W] . . . [1000W]
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.
Disabled
Remote Shutdown Delay
[No Delay] [1s] [2s] . . . [10800s]
No Delay
Delayed Shutdown Delay
[No Delay] [1s] [2s] . . . [10800s]
120s
Behavior on Rectifier Input Loss
NOTE Available only in >3000 VA
UPSs with separate supply sources
for the rectifier and bypass inputs.
[Prefer Battery] [Prefer Bypass]
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.
Prefer Battery
On Battery Notice Delay
[0] [1s] [2s] . . . [99s]
5s
* See “Configuring Bypass Settings” on page 44.