SPECIFICATIONS
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
74
Table 17. Environmental and Safety
120V Models
208/230/240V Models
Surge Suppression
ANSI C62.41 Category B3
(6 KV Ring and Combination)
EN 61000-2-2
EN 61000-4-2, Level 3
EN 61000-4-3, Level 2
EN 61000-4-4, Level 2 (also on signal ports)
EN 6100-4-5, Level 3 Criteria A
EN 61000-4-6, Level 2
EN 61000-4-8, Level 2
EN 6100-4-11
EMC Certifications
<1500 VA: FCC Class B, VCCI Class B,
EN 55022 Class B
3000 VA: FCC Class A, VCCI Class A,
EN 55022 Class A
CE per IEC/EN 62040-2,
Emissions: Category C1,
Immunity: Category C2
EMC (Emissions)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety Conformance
UL 1778, IEC 62040-1-1, IEC 60950-1
Agency Markings
CE, UL, CUL, NOM
Operating Temperature
0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE Thermal protection switches load to Bypass in case of overheating.
Storage Temperature
-20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit Temperature
-25°C to 55°C (-13°F to 131°F)
Relative Humidity
5–90% noncondensing
Operating Altitude
Up to 3,000 meters (9,843 ft) above sea level
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
<50 dBA at 1 meter typical
Leakage Current
<1.5 mA