SPECIFICATIONS
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
75
Table 18. Battery Runtimes (in Minutes) at 100% Load
Model
Internal Batteries
+ 1 EBM
+ 2 EBMs
+ 3 EBMs
+ 4 EBMs
1000 VA, 120V
5
30
55
83
108
1000 VA, 208/230/240V
7
29
51
81
98
1500 VA, 120V
5
23
48
67
91
1500 VA, 208/230/240V
5
24
44
72
89
3000 VA, 120V
3
20
36
53
71
3000 VA, 208/230/240V
3
18
34
53
69
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 19. Battery
Internal Batteries
EBMs
Configuration
700–1000 VA models: 36 Vdc (3 12V, 9 Ah)
1500 VA models: 48 Vdc (4 12V, 9 Ah)
3000 VA models: 72 Vdc (6 12V, 9 Ah)
1000 VA models: 36 Vdc (2x3 12V, 9 Ah)
1500 VA models: 48 Vdc (2x4 12V, 9 Ah)
3000 VA models: 72 Vdc (2x6 12V, 9 Ah)
Fuses
Not applicable
(4) 30A/125 Vdc fuses per EBM
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
Internal batteries: 3 hours
1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours
Battery Port
External three-pole Anderson connector on UPS for connection to EBM