INSTALLATION
Avaya 9135 6000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201769 Rev 1
30
Tower Setup
C A U T I O N
S
DO NOT install the UPS or EBM in a hermetically-closed environment without any
exchange of air.
S
The UPS and EBM are heavy (see page 61). A minimum of two people are required to lift
the cabinets into the pedestals.
The setup varies depending on the number of cabinets you are installing:
1.
Assemble the UPS pedestals (see Figure 11).
Figure 11. Assembling the UPS Pedestals
2.
For one cabinet,
the pedestals must be installed. Continue to Step 3.
For two or more cabinets,
the pedestal extenders and the joining
brackets must be installed. Proceed to Step 6.
NOTE
Always keep 150 mm free space behind the UPS rear panel. The distance between
the tower stands should be 450 mm.
3.
Carefully position the cabinet upright with the UPS indicators at the
top and place in the pedestals (see Figure 12).
4.
Adjust the pedestals to the size of the UPS and secure the
pedestals with the captive screws.