Additional maintenance procedures
Analog tie trunk back-to-back testing
384
Maintenance Procedures
December 2003
Figure 115: Trunk Group form - E & M mode (Page 2 of 2)
10
Locate the tie trunk port terminal connections at the cross-connect field. Consult the appropriate
table below for either 110-type or 66-type hardware.
11
At the cross-connect field, disconnect outside trunk facilities from the tie trunk ports and mark the
disconnected wires for reconnecting the tie trunk ports to their normal configuration later. The D
impact tool (AT-8762) is required to perform this step.
12
Use jumper wires (DT 24M-Y/BL/R/G and DT 24P-W/BRN) and the D impact tool to connect
wiring between the two ports assigned in
at the cross-connect field. For example, if the two
ports on the analog Tie Trunk circuit pack are port 1 and 2, connect the wirings as shown below:
13
Check all wirings to verify good connections between the two test ports.
Page 2 of 5
TRUNK GROUP
GROUP MEMBER ASSIGNMENTS
Port Name Mode Type Answer Delay
1: B1901 E & M t1 stan
2: B1902 E & M t1 comp
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
14:
15:
Port 1
(t1 stan)
(E&M)
Port 2
(t1 comp)
(E&M)
T1
connected to
T12
R1
connected to
R12
T11
connected to
T2
R11
connected to
R2
E1
connected to
M2
M1
connected to
E2