System 75 Small-Cabinet to R8si (Blowback)
Task List: System 75 Small Cabinet to R8si
SI Installation and Upgrades
315
June 2004
The results of system tests display on the monitor.
3
Verify that all tests pass.
If any of the terminal messages indicate a test has failed or if the message
spe down mode
is
displayed, refer to Maintenance for Avaya DEFINITY® Server SI (555-233-123) to clear the
trouble.
4
Type
set time
and press Enter.
See
Figure 87
.
5
Enter the date information and the time in 24-hour format. Enter either
daylight saving time
or
standard time
, depending on the current time in your time zone. If your area does not use
daylight saving time, set the value of
Daylight Savings Rule
to 0; otherwise, set
Daylight Savings Rule
to 1. Press Enter to set the date and time and ensure that the
system boots properly.
Figure 87: Typical Date and Time Screen
Return to Task List
Enable customer option and alarm origination [75 small upgrade]
Return to Task List
NOTE:
This procedure requires an init login.
If the upgrade is after hours, coordinate with the regional CSA to have the features turned on.
DC
1
At the DC Battery Cabinet (if installed), set the circuit
breaker to ON.
2
At the DC Power Cabinet, set the circuit breaker(s) on the
rectifiers to ON.
This starts the system initialization and test. Some red
LEDs may be turned on, but they are turned off during the
boot-up process. No action is required.
DATE AND TIME
DATE
Day of the Week: Tuesday Month: June
Day of the Month: 26 Year: 2000
TIME
Hour: 20 Minute: 30 Second: XX Type: standard
Daylight Savings Rule: 1
System
Steps