UPS Startup
29
Avaya
t
RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual
S
164201543 Rev A
6.
The system signals an alarm when the required output cannot
be maintained with the loss of redundant power modules. The
alarm is essentially disabled with a redundancy level set at 0.
If you want the system to notify you when the number of
redundant power modules is less than a specified level, enter a
redundancy level. Each increment above 0 indicates the
number of modules that can be removed from operation before
the alarm occurs. This setting only affects the alarm; the system
continues to operate as an N+X system even if this parameter is
left at the default value of 0.
Set Redundancy
RSetting
0
<-
->
ESC
7.
To password-protect the UPS On/Off function, press the
Y
or
B
button to make your selection; then press the
button. If a
password is required, the UPS On and Off functions are
accessible only after first entering the correct password value
(0377).
ON OFF Password?
No
ESC
8.
The UPS is now ready to operate, and displays the normal
On/Off function screen.
These configuration parameters are accessible during normal
UPS operation by pressing the Config button through the front
panel display.