Specifications
50
Avaya
t
RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual
S
164201543 Rev A
Table 9. Split-Phase Model Specifications
9 kVA, 7500 Watts
Voltage
Input Current*
Output Current
Input Service**
Heat Dissipation
Normal Mode
100/200
48A
45A
110/220
45A
41A
120/208
42A
43.5A
60A
860W (2.93 kBTU/hr)
127/220
39A
41A
(
/ )
120/240
42A
37.5A
12 kVA, 10000 Watts
Voltage
Input Current*
Output Current
Input Service**
Heat Dissipation
Normal Mode
100/200
64A
60A
110/220
60A
55A
120/208
56A
58A
80A
1145W (3.90 kBTU/hr)
127/220
52A
55A
(
/ )
120/240
56A
50A
15 kVA, 12500 Watts
Voltage
Input Current*
Output Current
Input Service**
Heat Dissipation
Normal Mode
100/200
80A
75A
110/220
75A
70A
120/208
70A
72.5A
100A
1430W (4.88 kBTU/hr)
127/220
65A
70A
(
/ )
120/240
70A
62.5A
*In Bypass modes the input current equals the output current plus 2A for each power module in the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power
module.
**To accommodate the feature of easy system expandability, it is recommended that initial installation of the Avaya RS9
UPS contain wiring to support the maximum capacity of the UPS cabinet. If you are installing a battery charger module,
refer to the input circuit breaker requirements in Table 1 on page 12.