Maintenance-Object Repair Procedures
555-233-143
8-388
Issue 1 May 2002
Cabinet Temperature Query Test (#122)
This test queries an EPN’s Maintenance circuit pack for the status of the
temperature and fan sensors in the cabinet.
Table 8-162.
Test #122 Cabinet Temperature Query Test
Error
Code
Test
Result
Description / Recommendation
1000
ABORT
System resources required to run test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABORT
Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort with error code 2000, check for power
problems with the EPN’s A carrier. Look for and resolve every
AC-POWER and CARR-POW alarm in a multicarrier cabinet or
DC-POWER alarm in a single-carrier cabinet. Repeat the test.
3. If the test continues to abort with error code 2000, check for and resolve
every MAINT error in an EPN. Repeat the test.
2029,
2319,
2500
ABORT
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...