Maintenance-Object Repair Procedures
555-233-143
8-394
Issue 1 May 2002
AC-Powered Cabinets
AC Power-Distribution Unit and Battery
Charger (J58890CE-2)
shows an AC power-distribution unit (List 9 or List 10).
This unit sits at the bottom of some multicarrier cabinets.
Carrier Port Power Supplies
—
Multicarrier Cabinets
Code
System
Power
Output (VDC)
Location
631DA
AC
+5
Left side
631DB
AC
-48/-5
Right side
644A
DC
+5
Left side
645B
DC
-48/-5
Right Side
TN755B
165
Slots 17 and 18
631WA/AR
AC
+5
Left side
631WB/BR
AC
-48
Right side
TN736
AC
-5
Used with 631
TN752
AC
165/-5
WA/WB or AR/AB
649A
AC
-48 at 10 Amps
+5 VDC and -5
VDC at 6 Amps
Right side on control and port
carriers. Left and right side on switch
node carriers.