DC-POWER (Single-Carrier Cabinet Environment)
Issue 1 May 2002
8-499
555-233-143
If a Carrier Port Power Supply is physically removed from a carrier in a
single-carrier cabinet, there will not be a DC-POWER alarm. DC-POWER
maintenance cannot distinguish between removal of the power supply and the
physical absence of the cabinet.
There is a nominal power holdover of .25 second in an PN single-carrier cabinet.
Hardware Error Log Entries and Test to Clear
Values
Table 8-202.
Single-Carrier Cabinet Power Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
1
1.
UU is the universal cabinet number indicated in the
PORT
field of the Alarm Log.
0
2
2.
Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0
Any
Any
Any
test environment UU
513
0 or 1
‘‘Single-Carrier Cabinet
Power Query Test (#79)’’
MAJOR
ON
test environment UU r 2