EXT-DEV ADMIN? Y (External Device Alarm)
Issue 1 May 2002
8-827
555-233-143
EXT-DEV ADMIN? Y (External Device
Alarm)
NOTE:
Use this MO when the External Device Alarm Admin? field on the change
system-parameters customer-options form is set to (y). You must have
INADS or INIT login permissions to administer EXT-DEV Alarm.
Each PN’s Maintenance circuit pack has two alarm ports that connect to such
external devices as uninterruptible power supplies (UPSs) or adjuncts (e.g.,
AUDIX).
Certain conditions on the external device close the contacts on the alarm leads to
notify the switch that in turn originates an EXT-DEV alarm. One set of leads
generates a major alarm; the other set generates a minor alarm.
The special locations UUmajor and UUminor are used to designate the major or
minor Maintenance board’s alarm connection for cabinet UU. The major/minor
designation specifies the port, not the alarm level associated with the connection;
for example, the “major” port can be administered as a major, minor, or warning
alarm, and the “minor” port can be administered as a major, minor, or warning
alarm. In addition Analog line ports can also be administered as external device
alarms.
NOTE:
An unadministered Maintenance board’s external device alarm port, that is
sensing a contact closure will have an entry in the Error Log and in the
Alarm Log. The alarm receiver will not receive warning alarms.
MO’s Name (in
Alarm Log)
Alarm
Level
Initial SAT Command to Run
1
1.
UU is a cabinet number determined in the
Port
field of the Alarm or Error Log.
Full Name of MO
EXT-DEV
MAJOR
test eda-external-device-alrm
physical-location
External Device Alarm
EXT-DEV
MINOR
test eda-external-device-alrm
physical location
External Device Alarm
EXT-DEV
WARNING
test eda-external-device-alrm
physical-location
External Device Alarm
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...