Maintenance-Object Repair Procedures
555-233-143
8-842
Issue 1 May 2002
Table 8-327.
Test #757 SNI Destructive Facility Test
Error
Code
Test
Result
Description / Recommendation
1015
ABORT
The system will not allow this test to be run because the fiber link has not been
busied out. Busyout the fiber link with busyout fiber-link F P. Repeat the test
fiber-link F P long command.
2100
ABORT
Could not allocate the necessary system resources to run this test.
2300
ABORT
The downlink message necessary to run this test could not be sent.
2301
ABORT
The software timer could not be set before sending the downlink message
necessary to run this test.
2304
ABORT
SNI circuit pack responded that it is not able to run the test requested by
software.
1. Retry the command at 1-minute intervals up to 3 times.
2306
ABORT
A fiber link’s SNI circuit pack is not responding to test requests sent by
software.
1. Run the test led switch-node for the switch node where the SNI board(s)
reside to verify whether their LEDs light. If not, continue with the following
steps.
2. If LEDs light on other boards in the same carrier (but not on this board),
issue test board UUCSS l (#760) for the active SNC in this carrier. Wait 5
minutes, and try step 1 again. If the board’s LEDs still do not light, replace
the board. (Replacing an SNI may be service interrupting. Refer to the
SNI-BD section for the procedure to replace an SNI.)
3. If no LEDs light on any board in the same carrier, fix any connectivity
problems between this carrier and the media server. (Use list fiber-link to
determine the fiber connections to this carrier.) Check the LEDs on every
SNI and EI, and fix any fiber problems. Enter display errors, and resolve
any SYNC, SNI-BD, SNC-BD, FIBER-LK, or SNI-PEER error entries.
127
FAIL
The data is not correctly looped around on Endpoint 1 of the fiber link (list
fiber-link can be used to display fiber link endpoints).
1. Replace the SNI circuit pack.
227
FAIL
The data is not correctly looped around on Endpoint 2 of the fiber link (list
fiber-link can be used to display fiber link endpoints).
1. Replace the SNI circuit pack.
PASS
No problems associated with this test are detected on the SNI(s).
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...