MET-LINE (MET Line)
Issue 1 May 2002
8-1099
555-233-143
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This could be
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
config command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the busyout
board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the linkage
between the internal ID and the port. If this is not the case, check to
ensure that there is a valid board inserted.
Table 8-451.
Test #56 MFAT Electronic Power Feed Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page