DS1 CPE Loopback Jack (T1 Only)
Issue 1 May 2002
5-5
555-233-143
9. Repeat
as desired to observe bit error rate
characteristics. Also, wait 1 to 10 minutes between
. One
minute without errors translates to better than a 1 in 10 to the eighth error
rate. Ten minutes without errors translates to better than a 1 in 10 to the
ninth error rate.
10. If the test runs for 1 minute with an error count of 0, confirm that the 3-in-24
pattern error detector is operating properly by entering test ds1-loop
location inject-single-bit-error. This causes the 3-in-24 pattern
generator on the DS1 circuit pack to inject a single-bit error into the
transmit pattern. A subsequent list meas ds1 summary location
command displays the bit error count:
■
If a count greater than 1 is displayed, replace the ICSU and retest.
■
If the problem continues, replace the DS1 circuit pack.
Table 5-1.
DS1 Span Troubleshooting
Displayed Field
Function
Indication
Test:
cpe-loopback-jack
Pattern 3-in-24
The loopback jack test is active.
Synchronized
Y or N
■
If “y” displays, the DS1 circuit pack has synchronized
to the looped 3-in-24 pattern and is accumulating a
count of the bit errors detected in the pattern until the
test has ended.
■
If “n” displays, retry the test five times by ending the
test per
and re-starting the test per
■
If the circuit pack never synchronizes, substantial bit
errors in the 3-in-24 pattern are likely. This could be
intermittent connections or a broken wire in a receive
or transmit pair in the CPE wiring.
Bit Error Count
Cumulative
count of
detected errors
If there are no wiring problems, the counter remains at 0.
A count that pegs at 65535 or continues to increment by
several hundred to several thousand on each list meas
command execution may indicate:
■
Intermittent or corroded connections
■
Severe crosstalk
■
Impedance imbalances between the two conductors
of the receive pair or the transmit pair. Wiring may
need replacement.
Note that “ESF error events” counter and the ESF
performance counter summaries (“errored seconds”,
“bursty errored seconds”, and so forth) will also increment.
These counters are not used with the loopback jack tests.
However, they will increment if errors are occurring.
Counters should be cleared following the test.
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...