RDIG-STA (Remote Digital Station)
Issue 1 May 2002
8-1351
555-233-143
DIG-LINE Station Lamp Updates Test (#16)
This test lights every lamp on the terminal as specified. The lamp updates will run
only if the station is in-service. The status of the station is checked and the lamp
updates are blocked from taking place, if the station is not in the in-service state.
This test does not affect the status of the Message Waiting lamp.
Table 8-547.
Test #16 DIG-LINE Station Lamp Updates Test
Error
Code
Test
Result
Description / Recommendation
ABORT
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
1
ABORT
This port may have been busied out by system technician.
1. Look in the Error Log for Error Type 18 (port busied out) for this port. If this
error type is present, then release the port using the release station
extension command and run the test again.
2. Make sure that the terminal is connected.
3. Retry the command at 1-minute intervals up to 5 times.
3
ABORT
Station may be in ready-for-service or out-of-service state.
1. Use the status station command to verify the state of the station.
2. Make sure the terminal is connected.
3. Retry the command at 1-minute intervals up to 5 times.
1000
ABORT
System resources required to run this test are not available. The port may be
busy with a valid call. Use display port UUCSSpp to determine the station
extension or attendant number of the port. Use status station or status
attendant to determine the service state of the port. If the port is in use, wait
until the port is idle before testing. Attendants are always in use (off-hook) if
the handset is plugged in and the port is not busied out.
1. If the port status is idle, then retry the command at 1-minute intervals up to
5 times.
1392
ABORT
The port is currently a TTI port and the test will not execute on it.
1. Verify that the port is a TTI port using either the display port command
(the display shows that the port is a TTI port) or the list config command
(the display shows a
t
for the port).
2. If either list config or display port indicates that the port is not a TTI port,
escalate the problem. If both commands indicate that the port is a TTI port,
the abort is correct, and no action is necessary.
FAIL
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...