Maintenance-Object Repair Procedures
555-233-143
8-1498
Issue 1 May 2002
Stratum-3 Clock LED Strategy
NOTE:
When looking in the Stratum-3 cabinet, ‘‘A’’ card is on the left and ‘‘B’’ card is
on the right.
NOTE:
The normal LED scheme is not followed for this device. Green LEDs do not
indicate maintenance activity. There are no yellow LEDs, and there are
more than three LEDs per circuit pack.
NOTE:
Removal of a card in the Stratum-3 clock may cause alarm(s) to be resolved
and the query test to pass. However, the removed cards should still be
replaced to restore the Stratum-3 clock to full service.
The Stratum-3 clock has the following components:
■
2 Clock Input cards (CI)
Provides the logic to select the better DS1 reference or Clock Input card.
The red FAIL LED on this card indicates a failure with the card or the DS1
reference connected to it.
■
2 Stratum-3 Cards (ST3)
Provides 24-hour holdover. The red FAIL LED on this card indicates a
failure with the card. Replace the card.
■
2 Timing Output Cards (TOC)
Provides cable length compensation, multiple output ports, selection of the
ST3, and CI outputs. This type of card has two red failure LEDs: one
indicates a failure of the card; the other indicates a failure in one or more
output ports. In either case, replace the card.
■
1 PBX (Private Branch Exchange) Alarm Interface (PAI)
Filters power supplied to the clock, provides fuse protection, and provides
alarm indications based on inputs supplied by other cards. The six LEDs
on this card provide indications for the six alarm or status conditions as
follows:
— Loss of DS1 reference A
— Loss of DS1 reference B
— Loss of one clock unit
— Loss of both clock units
— Loss of one power supply
— Loss of both power supplies
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...