Maintenance-Object Repair Procedures
555-233-143
8-1538
Issue 1 May 2002
Test command for the system links, test sys-link UUCSSpp can be specified with
current or faulted as an optional argument if the user wishes to test every
component in the specified path. The tests executed will be the same if the user
were to test each component manually. In the event that the user does not
specify any path, then only the tests specified for the system links are executed.
System Link Status (#985)
This test is nondestructive. This test queries the switch for the status of the
system link and verifies that every switch component has the same view of the link
state.
Order of Investigation
Short Test
Sequence
Long Test
Sequence
D/ND
1
1.
D = Destructive, ND = Nondestructive
System Link Status (#985)
X
X
ND
Table 8-596.
TEST #985 System Link Status
Error
Code
Test
Result
Description / Recommendation
1007
ABORT
Could not locate the system link associated with this location
1. Retry the command at 1-minute intervals up to 5 times.
2500
ABORT
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
6
FAIL
The system link is down.
1. Follow the procedure for Error Type 13.
PASS
The system link is up.
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...