ANL-16-L (16-Port Analog Line)
Issue 1 May 2002
8-59
555-233-143
2000
ABORT
Response to the test request was not received within the allowable time period.
2100
ABORT
Could not allocate necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
The terminal equipment is not connected to the circuit pack. Some terminal
equipment, such as modems, may fail even when connected properly.
1. Remotely test the equipment.
2. If the test fails again, look for RING-GEN errors in the Error Log.
3. Check all of the wiring between the station equipment and the switch.
Then, run the test again.
4. If the test still fails, the set may be defective. Check the set, and replace it,
if necessary.
5. Some terminal equipment could fail even when it is connected properly. If
this is the case, disable the test using the change station extension
command (enter n into the
Test?
field). Note that this action also
disables Tests 6, 7, 161, and 35 on this port.
PASS
The station is connected properly to the switch. This test may also pass if no
terminal equipment is connected and the terminal is located very far from the
switch. Investigate user-reported troubles on this port by using other port tests
or by examining the station and its wiring.
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This could be
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Verify that the board’s translations are correct. Use the list config
command, and resolve any problems.
2. If the board was found to be correctly inserted in step 1, issue the busyout
board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port. If
not, verify that a valid board is inserted.
Table 8-24.
Test #48 Station Present Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...