AN-LN-PT (Analog Line Port)
Issue 1 May 2002
8-111
555-233-143
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This result could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to make sure that the board translations are correct. Use the list
configuration command, and resolve any problems.
2. If the board is correctly inserted, issue the busy board UUCSS command.
3. Issue the reset board UUCSS command.
4. Issue the release board UUCSS command.
5. Issue the test board UUCSS long command.
This should re-establish the link between the internal ID and the port. If
not, verify that a valid board is inserted.
Table 8-42.
Test #35 Battery Feed Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page