ASAI-PT
Issue 1 May 2002
8-155
555-233-143
ASAI-PT
Unless otherwise stated, every maintenance action contained in this section
applies to ASAI-PT and ISDN-BRI ports connected to ASAI adjuncts. This port
type is administered as an ASAI-BD on the TN800 circuit pack.
The TN800 circuit pack is a PC-based platform that allows interaction of multiple
applications with an S8700 Multi-Connect system. MultiVantage software (Native
mode) supports emulation of three types of port MOs on this board. The type of
ports to be emulated are defined by the applications running on the TN800. The
TN800 can support up to 32 ports (time slots) at a time.
The TN800 connects to the switch through a single slot in the backplane, however
its width is not limited to one slot. The number of slots occupied by the TN800 is
supplied by the board during its insertion. The TN800 (Release 5 and higher) is
three slots wide. The blank (reserve) slots are to the left of the functional slot.
In non-native mode the TN800 is recognized as TN556, TN2181, TN754, or
TN746 based on the switch software and the application running on the TN800.
In non-native mode only one type of port MO runs at any time, and the port type
depends on the application running on the TN800. If the TN800 fails diagnostics
in non-native mode, the system’s alarm and error logs would show a failure for the
board type the TN800 is emulating.
MO’s Name (in
Alarm Log
Alarm Level
Initial Command to
Run
1
1.
Where UU is the universal cabinet number (1 – 44 for EPNs); C is the carrier designation (A, B, C,
D, or E); SS is the address of the slot in the carrier where the circuit pack resides (1 – 21); and pp
is the 2-digit port number (01, 02, 03, ...).
Full Name of MO
ASAI-PT
MAJOR
2,3
2.
The alarm level for ASAI adjunct ports may be administered using the set options command. The
alarm level can be set independently for on- and off-board alarms to WARNING, MINOR, or
MAJOR for every ASAI adjunct port in the system.
3.
All alarming for an ASAI adjunct and off-board alarming for an ASAI port is disabled if the ASAI
adjunct asks the switch to suspend maintenance. When this occurs, an error and a WARNING
alarm is logged against the ASAI adjunct. Check the Hardware Error and Alarm Logs to see if the
adjunct has disabled alarming.
test port UUCSSpp l
ASAI ISDN BRI port
ASAI-PT
WARNING
test port UUCSSpp l
ASAI ISDN BRI port
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...